WAC 296-835-13020   Take additional precautions if your roll coating operation uses a liquid that has a flashpoint below 140°F (60°C).  

     IMPORTANT:

     This section applies to the processes of roll coating, roll spreading, or roll impregnating that use a liquid having a flashpoint below 140°F (60°C). Material may be passed directly through a tank or over the surface of a roller that revolves partially submerged in the liquid.

     You must:

     • Prevent sparks from static electricity by:

     – Bonding and grounding all metallic parts (including rotating parts) and installing static collectors

     OR

     – Maintaining a conductive atmosphere (one with a high relative humidity, for example) in the vapor area.



[Statutory Authority: RCW 49.17.010, [49.17].040, and[49.17].050 . 02-15-102, § 296-835-13020, filed 7/17/02, effective 10/1/02.]