WAC 296-835-12060   Make sure a heating system used for drying objects does not cause a fire.  

     You must:

     • Make sure the heating system used in a drying operation that could cause ignition:

     – Has adequate mechanical ventilation that operates before and during the drying operation

     – Shuts down automatically if a ventilating fan fails to maintain adequate ventilation

     – Is installed as required by NFPA 86-1999, Standard for Ovens and Furnaces.

Note: Some, or all, of the consensus standards (such as ANSI and NFPA) may have been revised. If you comply with a later version of a consensus standard, you will be considered to have complied with any previous version of the same consensus standard.




[Statutory Authority: RCW 49.17.010, [49.17].040, and[49.17].050 . 02-15-102, § 296-835-12060, filed 7/17/02, effective 10/1/02.]