WAC 296-835-12015
Provide bottom drains.
Exemption:
A bottom drain is not required if:
– The viscosity of the liquid makes it impractical to empty the tank by gravity or pumping
OR
– The dip tank has an automatic closing cover that meets the requirements of WAC
296-835-12025
.
You must:
• Provide a bottom drain on all dip tanks that hold more than five hundred gallons of liquid.
• Make sure the bottom drain:
– Is properly trapped
– Will empty the dip tank during a fire
– Has pipes large enough to empty the tank within five minutes
– Uses automatic pumps if gravity draining is not practical
– Is capable of both manual and automatic operation
– Discharges to a safe location.
Note:
Discharges to a safe location could be a:
– Safe location outside the building
OR
– Closed, properly vented salvage tank or tanks that can hold more than the dip tank.
You must:
• Make sure manual operation of the bottom drain is performed from a safe and easily accessible location.
[Statutory Authority: RCW
49.17.010
,
49.17.040
,
49.17.050
,
49.17.060
. 07-03-163, § 296-835-12015, filed 1/24/07, effective 4/1/07. Statutory Authority: RCW
49.17.010
,
[49.17].040
, and
[49.17].050
. 02-15-102, § 296-835-12015, filed 7/17/02, effective 10/1/02.]