WAC 296-835-11025   Periodically inspect your dip tanks and associated equipment and correct any deficiencies.  

     You must:

    
• Inspect or test your dip tanks and associated equipment periodically, including:

     – Covers

     – Overflow pipes

     – Bottom drains and valves

     – Electrical wiring, equipment, and grounding connections

     – Ventilating systems

     – Fire extinguishing equipment

     • Inspect the hoods and ductwork of the ventilation system for corrosion and damage and make sure the airflow is adequate:

     – At least quarterly during operation

     – Prior to operation after a prolonged shutdown

     • Promptly fix any deficiencies found.

Note: • To assist you in tracking your inspections and actions taken from those inspections, you may want to keep a written record.
• It is recommended that inspections be at least quarterly even if the system is not operating. Depending on the chemicals in use more frequent inspection may be required.




[Statutory Authority: RCW 49.17.010, [49.17].040, and[49.17].050 . 02-15-102, § 296-835-11025, filed 7/17/02, effective 10/1/02.]