| If you have: |
Then make sure they: |
| Shut off valves
used as a means
of lock out for
inspection or
repair |
Are of adequate flow capacity |
| Are arranged to be locked or sealed
open and not closed except by an
authorized person who does both of
the following: |
|
• |
Remains there while the valve
is closed |
| |
• |
Locks or seals the valve open
when leaving the station. |
| Discharge line
and header |
Are designed to accommodate the
maximum flow. |
|
Have a back pressure not greater
than ten percent of the design
pressure of the storage container |
|
Include the back pressure in the one
hundred twenty percent of the
maximum pressure of the design
pressure. |
|
Do not have other containers or
systems that exhaust into the
discharge line or header. |
|
Have vent lines installed to prevent
the accumulation of liquid in the
lines |
| |
Note: Multiple safety relief valves
on the same storage unit may be run
through a common discharge header. |
| Vacuum breakers |
Are provided with atmospheric
storage |
| Stacks |
Do both of the following: |
|
• |
Prevent any obstructions by
rain, snow, ice, or
condensation; |
|
|
AND |
|
• |
Have an outlet size not smaller
than the size of the safety relief
valve outlet connection |