Compressors for refrigerated systems.
You must:
• Make sure condensers are designed:
– For at least 250 psig;
AND
– To manually or automatically purge noncondensibles.
Note:
• Condensers may be cooled by any of the following:
– Air
– Water
– Air and water.
You must:
• Make sure compressors used for refrigerating ammonia meet all of the following:
– Are connected to plant piping with shut off valves located as close as practical to compressor connections
– Have a safety relief valve that is both:
▪ Large enough to discharge the full capacity of the compressor;
AND
▪ Connected to the discharge and placed before any shut off valve
– Have an oil separator on the discharge side, where necessary to prevent contamination.
– Have a drainable liquid trap or other adequate method on the compressor suction to minimize the entry of liquids into the compressor.
– Pressure gauges on the suction and discharge ends graduated to at least one and one-half times the maximum pressure that can develop.