WAC 296-826-40035
Refrigeration load.
You must:
• Make sure the total refrigeration load includes the loads imposed by all of the following:
– Heat flow into the container caused by the temperature difference between both:
▪ The ambient temperature;
AND
▪ The design storage temperature
– Heat flow into the tank caused by maximum sun radiation
– Filling the tank with ammonia warmer than the design storage temperature.
• Provide emergency power capable of handling loads imposed by both of the following:
– The temperature difference between the ambient temperature and the design storage temperature;
AND
– Sun radiation.
Note:
Emergency power is not necessary for facilities able to effectively vent vapors when the refrigeration system is not operating.
[Statutory Authority: RCW
49.17.010
,
49.17.040
,
49.17.050
,
49.17.060
. 06-10-067, § 296-826-40035, filed 5/2/06, effective 9/1/06.]