WAC 296-826-40030
Refrigerated storage compressors.
You must:
• Make sure compressors have all of the following:
– Their own driving unit
– Discharge pressure that is governed by the condensing
conditions
– Suitable compressor operation controls based on the
load pressure in the container
– At least two compressors either of which is of
sufficient size to handle the intended loads
– Standby equipment equal to the largest normally
operating piece of equipment installed when more than two
compressors are provided
– Automatic controls installed to prohibit the operation
of alternate compressors unless the controls will function
with alternate compressors.
• Make sure compressors are sized to operate with a
suction pressure that is both of the following:
– At least ten percent below the minimum setting of the
safety relief valves on the storage tank
– Able to withstand one hundred twenty percent of the
design pressure of the tank.
• Install an oil separator of suitable size in the
compressor discharge line that is both:
– Designed for at least 250 psig;
AND
– Equipped with a drain valve and gauging device.