WAC 296-826-40015
General requirements for all systems.
You must:
• Prohibit the use of cast iron fittings.
– The use of malleable or nodular iron such as
Specification ASTM A47 or ASTM A395 is permitted.
• Make sure all metal flexible connections for permanent
installations have a minimum working pressure of 250 psig
• Make sure all pipes, tubes, and fittings used for
ammonia service meet all of the following:
– Made of material with a design pressure at least equal
to the maximum service pressure.
– Well supported and have provisions for all of the
following:
▪ Expansion
▪ Contraction
▪ Vibration
▪ Jarring
▪ Settling.
• Protect all exposed pipes from damage resulting from
undue strain including:
– Moving machinery
– The presence of vehicles.
• Use ammonia resistant joint compounds.
• Make sure, after assembly, that all piping and tubing
are leak free at a pressure not less than the normal operating
pressure of the system.
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050,
49.17.060. 06-10-067, § 296-826-40015, filed 5/2/06,
effective 9/1/06.]