WAC 296-307-25042
What protection must an employer provide
for wall openings? (1) Wall opening barriers (rails, rollers,
picket fences, and half doors) must be constructed and mounted,
to withstand a load of at least two hundred pounds applied in any
direction (except upward) at any point on the top rail.
(2) Wall opening grab handles must be at least twelve inches
long and must be mounted to give 1-1/2 inches clearance from the
side framing of the wall opening. The size, material, and
anchoring of the grab handle must form a structure that can
withstand a load of at least two hundred pounds applied in any
direction at any point of the handle.
(3) Wall opening screens must be constructed and mounted to
withstand a load of at least two hundred pounds applied
horizontally anywhere on the near side of the screen. They must
be of solid construction, of grillwork with openings a maximum of
four inches long, or of slatwork with openings a maximum of two
inches wide and any length.
[97-09-013, recodified as § 296-307-25042, filed 4/7/97,
effective 4/7/97. Statutory Authority: RCW 49.17.040,[49.17.]050
and [49.17.]060. 96-22-048, § 296-306A-25042, filed
10/31/96, effective 12/1/96.]