WAC 296-307-073
What requirements apply to changing and
charging storage batteries? (1) Battery changing installations
must be located in areas designated for that purpose.
(2) Facilities must be provided for:
• Flushing and neutralizing spilled electrolyte;
• Fire protection;
• Protecting charging apparatus from damage by trucks; and
• Adequate ventilation of fumes from gassing batteries.
(3) Racks used to support batteries should be made of or
covered with materials that will not create sparks.
(4) A conveyor, overhead hoist, or equivalent material
handling equipment must be provided for handling batteries.
(5) Reinstalled batteries must be properly positioned and
secured in the vehicle.
(6) A carboy tilter or siphon must be provided for handling
electrolyte.
(7) When mixing water and acid for charging batteries, pour
acid into water; do not pour water into acid.
(8) Vehicles must be properly positioned and the brake
applied before attempting to change or charge batteries.
(9) When charging batteries, the vent caps should be kept in
place to avoid electrolyte spray. You must ensure that vent caps
function. The battery (or compartment) cover(s) must be open for
cooling.
(10) Precautions shall be taken to prevent open flames,
sparks, or electric arcs in battery charging areas.
(11) Tools and other metallic objects must be kept away from
the tops of uncovered batteries.