WAC 296-150V-1460
What requirements apply to testing for
gas piping leaks after conversion vendor unit or medical unit
appliances are connected? (1) After gas appliances have been
connected, the gas-piping system must be subjected to a
pressure test with the burner valves closed. The test
consists of air at not less than ten inches nor more than
fourteen inches pressure of water column (six to eight
ounces). The system must hold this pressure for a period of
not less than ten minutes with no leakage. Before beginning
the test, the temperature of the gas-piping system and the
test air must be equalized, and this shall be maintained
throughout the test.
(2) Appliance shut-off valves ahead of gas cooking
appliances may be closed for the performance of this test.
When the test is satisfactorily performed, these valves must
be opened and, while the system is under pressure, the
appliance connectors must be tested with an approved leak
detector or approved bubble solution.
[Statutory Authority: Chapter 43.22 RCW. 99-18-069, §
296-150V-1460, filed 8/31/99, effective 10/1/99.]