WAC 296-150V-1440
Are gas piping shut-off valves required in
a conversion vendor unit or medical unit? (1) In addition to any
valve on the appliance, a shut-off valve must be installed in the
fuel piping outside of each gas appliance but inside the conversion
vendor unit or medical unit structure and upstream of the union or
connector. The shut-off valve must be located within six feet of
a cooking appliance and within three feet of any other appliance.
A shut-off valve may serve more than one appliance if located as
required above.
(2) Shut-off valves used in connection with gas piping must be
of a type designed for use with liquefied petroleum gas. Shut-off
valves must be tested and approved to ANSI Z21.15 standard or
equal.
[Statutory Authority: Chapter 43.22 RCW. 99-18-069, §
296-150V-1440, filed 8/31/99, effective 10/1/99.]