WAC 296-150M-0550
What is required to meet the fire
safety certificate requirements? You will need to complete
the following requirements for your pre-HUD home.
(1) Wiring system. Aluminum wiring is not permitted for
use in fifteen and twenty amp branch circuits. You must do
one of the following:
(a) Rewire the fifteen and twenty amp branch circuits in
copper.
(b) Install receptacles and switches that are approved
for the use of either aluminum or copper (i.e., they will be
marked AL/CU); or
(c) Install copper "pig tail" connections using wiring
nuts approved for aluminum wire between the aluminum wire and
the receptacle/switch/light fixture/bath and fans/range hoods.
Additionally, if the circuit breakers in the electrical
panel for fifteen and twenty amp circuits are not approved for
aluminum wiring, the breakers either need to be replaced with
those that are acceptable for aluminum wire or they need to be
pit tailed with copper wire and wire nuts acceptable for
aluminum wire.
(2) Fire protection.
(a) Walls, doors and ceilings in the water heater and
furnace compartments shall be protected by materials with a
flame spread rating not exceeding twenty-five. (This can be
met with gypsum wallboard having a minimum thickness of 5/16
inch or ceramic tile.)
(b) The range hood must be at least as wide as the
appliance and have a lower front edge or "eyebrow" which
extends at least three inches past the cabinet above.
(c) The surfaces of the exposed walls adjacent to and
within six inches of a range or cooktop appliance must be
composed of gypsum wallboard, with a minimum thickness of 5/16
inch, or ceramic tile. Kitchen cabinets constructed of
combustible material that is located above a range or cooktop
must be a minimum of twenty-four inches above the cooking
surface. The cabinets must be protected on the bottom and on
the exposed sides within six inches of either side of the
appliance, by covering the surface with gypsum wallboard, with
a minimum thickness of 5/16 inch, and installing a metal hood
above the cooking appliance. A minimum of 3/8 inch gap is
required between the cabinet and the gypsum on top of the
hood.
(d) No window may be within twelve inches of the edge of
a burner or element of the cooking appliance.
(3) Emergency egress.
(a) Every bedroom or other room designed expressly for
sleeping purposes must have a window that meets the minimum
requirements of at least 5.0 square feet of opening for
emergency egress.
(b) Rooms that have a door, with a minimum clear opening
of twenty-eight inches wide by seventy-two inches high, which
opens directly to the outside do not need to have an emergency
egress window.
(c) Windows and devices must be installed in a manner
which allows for proper operation.
(d) The bottom of the opening of an egress window shall
be no more than thirty-six inches above the floor.
(e) The height of the bottom of the window can be
increased to forty-four inches when the clear net area is
increased to 5.7 square feet of opening.
(4) Smoke detectors.
(a) Smoke detectors are required at each hallway or area
giving access to a bedroom or group of bedrooms. When a
furnace is located in the hall giving access to the bedrooms,
the detector is to be located between the living area and the
return air grill of the furnace.
(b) Smoke detectors must be installed on a wall and must
be permanently wired and installed on a J-box with splices
terminating inside the box.
(c) A smoke alarm with a rated life of ten years and
provided with a listed ten year battery can be used in lieu of
wired smoke detector.
(d) The smoke detector may not be switched and if more
than one smoke detector is installed, then each one is to be
wired on a different branch circuit.
(e) Smoke detectors do not need to be wired together to
sound simultaneous alarms.
[Statutory Authority: Chapter 43.22 RCW and 2005 c 399. 05-24-020, § 296-150M-0550, filed 11/29/05, effective 1/1/06.]