WAC 296-104-260
Installation -- What are the required
clearances for unfired pressure vessels? When unfired
pressure vessels are replaced or new vessels are installed in
either existing or new buildings, manufacturers'
recommendations shall be used, but in no case less than
eighteen inches shall be provided between the top of the
unfired pressure vessel and the ceiling and adjacent walls or
other structures. All unfired pressure vessels having
manholes shall have five feet clearance from manhole openings
and any wall, ceiling, or piping that will prevent a person
from entering the unfired pressure vessel.
[Statutory Authority: RCW 70.79.030, 70.79.040, 70.79.150,
70.79.290, 70.79.330, 70.79.350, and chapter 70.79 RCW. 02-23-036, amended and recodified § 296-104-260, filed
11/13/02, effective 12/14/02. Statutory Authority: RCW 70.79.030 and 70.79.040. 96-21-081, § 296-104-273, filed
10/16/96, effective 11/16/96.]