WAC 296-104-255
Installation --
What are the required clearances for boilers? When
boilers are replaced or new boilers installed in either
existing or new buildings, a minimum top clearance as
specified below shall be provided between the top of boiler
proper and ceiling. Sufficient access must be provided for
inspection, maintenance, operations, and repair. Required
clearances shall be:
(1) Minimum clearance on top of power boilers having a
steam generating capacity in excess of 5,000 pounds per hour
or having a heating surface in excess of 1,000 sq. ft. or
input in excess of 5,000,000 btu per hour
shall be 7 feet.
(2) Minimum clearance on top of low pressure heating
boilers which exceed any one of the following limits:
5,000,000 btu input; 5,000 lbs. steam per hour capacity or
1,000 sq. ft. heating surface; and power boilers which do not
exceed any of the following limits: 5,000,000 btu input;
5,000 lbs. steam per hour capacity or 1,000 sq. ft. heating
surface; shall be . . . . . . . . . . . . 3
feet.
(3) Minimum clearance on top of
boilers which do not exceed the above limits and miniature
boilers; shall be . . . . . . . . . . . . 2 feet.
(4) Minimum clearance from manhole openings and any wall,
ceiling, or piping that will prevent a person from entering
the boiler shall be . . . . . . . . . . . . 5 feet.
(5) Minimum clearances at sides, front and back wall
shall be the manufacturers' recommendations, but in no case
less than eighteen inches.