WAC 296-104-235
Construction -- What are the requirements for
code exempted boiler and unfired pressure vessel safety relief
valves? The boilers and unfired pressure vessels covered by WAC 296-104-230 shall be protected by the installation of ASME Code
relief valves with trial levers, set pressure not to exceed the
boiler's or the unfired pressure vessel's design pressure. Relief valves shall be installed on top of the boiler or the
unfired pressure vessel or on outlet piping as close as possible
to the boiler or unfired pressure vessel, with a minimum of
fittings and no valves intervening. The outlet of the relief
valve shall be run full size to a safe place and shall not induce
stress on the valve.
[Statutory Authority: RCW 70.79.030, 70.79.040 and chapter 70.79 RCW. 00-21-024, § 296-104-235, filed 10/10/00, effective
11/13/00. Statutory Authority: RCW 70.79.030 and 70.79.040. 96-21-081, § 296-104-235, filed 10/16/96, effective 11/16/96. Statutory Authority: RCW 70.79.030. 78-03-057 (Order 78-3), §
296-104-235, filed 2/22/78; Part IV, § 8, filed 3/23/60.]