WAC 296-99-080
How must continuous-flow bulk raw grain
dryers be equipped and installed? (1) The employer must
ensure that all direct-heat grain dryers have automatic
controls that:
(a) Shut off the fuel supply in case of power, flame, or
ventilation airflow shutoff; and
(b) Stop the grain flow into the dryer if the dryer
exhaust gets too hot.
(2) The employer must ensure that each direct-heat grain
dryer installed after March 30, 1988, is:
(a) Located outside the grain elevator; or
(b) When located inside the grain elevator, protected by
a fire or explosion suppression system; or
(c) Isolated by a structure with at least a one hour
fire-resistance rating.