WAC 296-99-060   How must filter collectors be installed?  (1) The employer must ensure that, on a pneumatic dust collection system, each fabric dust filter collector has a monitoring device that will show a pressure drop across the surface of its filter.

     (2) The employer must ensure that each filter collector installed after March 30, 1988, is:

     (a) Located outside the facility; or

     (b) When located inside the facility, protected by an explosion suppression system; or

     (c) Isolated by a structure with at least a one hour fire-resistance rating:


Next to an exterior wall;
Vented to the outside; and
The vent and ductwork must resist rupture from intense heat.