WAC 296-96-23810
What requirements apply to electrically
operated sidewalk elevators? Where the top opening is located
in the sidewalk or other area exterior to the building, all
electrical equipment on the car or in the hoistway must be
weatherproof. The operation of power sidewalk elevators
through openings in the sidewalk, or through openings in other
exterior areas which are protected by hinged doors or
vertically lifting covers, must conform to these following
requirements:
(1) The elevator must be operable in both the up and down
directions through the opening, only from the sidewalk or
other exterior area. The operations must be by means of:
(a) Key-operated continuous pressure type, up and down
switches; or
(b) Continuous pressure type up and down operating
buttons on the free end of a detachable, flexible cord five
feet or less in length.
(c) Continuous pressure type up and down operating
buttons may be installed on the elevator car providing the
control is so designed that the buttons will not function
unless the sidewalk doors are locked in the open position and
that a safety screen that will open and close with the car is
installed.
(2) Key-operated switches must be of continuous pressure
spring-return type, with the key removable only when the
switch is in the off position.
[Statutory Authority: RCW 70.87.020, 70.87.030, 70.87.034,
70.87.120, 70.87.185 and chapter 70.87 RCW. 01-02-026, §
296-96-23810, filed 12/22/00, effective 1/22/01.]