WAC 296-96-05030
What are the construction requirements
for hoistway enclosure gates and doors? Enclosure gates
(doors) must be constructed according to the following
standards:
(1) The gate must guard the full width of each opening on
every landing.
(2) It must be built in one of the following styles:
(a) Vertically sliding;
(b) Biparting;
(c) Counter-balanced;
(d) Horizontally swinging; or
(e) Horizontally sliding.
(3) Be constructed of either solid material or material
with openings that will reject a 2-inch diameter ball.
(4) Be constructed with a distance of not more than 2 1/2
inches between a hoistway gate or hoistway door face and a
landing sill edge.
(5) Be designed and guided to withstand (without being
broken, permanently deformed, or displaced from its guides or
tracks) a 100 pound lateral pressure applied near its center.
(6) Be equipped with labeled and listed electrical
interlock(s) that prevents the operation of the lift when the
doors or gates are open.
(7) Be constructed with balanced type
vertically sliding gates that extend no more than 2 inches
vertically from the landing threshold and no less than 66
inches above it.