WAC 296-96-02570
How do we enforce hoistway ventilation? (1) Area of vents. As required in International Building Code
(IBC) 3004.3.1 and chapter 51-50 WAC, the area of the vents
shall not be less than 3-1/2 percent of the area of the
hoistway nor less than three square feet (0.28 m2) for each
elevator car, and not less than 3-1/2 percent nor less than
one-half square foot (0.047 m2) for each dumbwaiter car in the
hoistway, whichever is greater. The total required vent area
shall be equipped with dampers that remain powered closed
until activated open by the fire alarm system panel. The
dampers shall open upon loss of power.
(2) Activation of the powered vent must not be from the
same device that activates the phase one fire recall.
EXEMPTION:
Special purpose and residential elevators are exempt from this section.