WAC 296-46B-701
Legally required standby systems.
008 Signs.
(1) The sign(s) required in NEC 701.8 must be placed at
the service disconnecting means and the meter base if the
service disconnecting means and meter base are not located
within sight and within 5' of each other.
018 Coordination.
(2) The requirements for selective coordination described
in NEC 701.18 are not required where the legally required
standby system was installed prior to June 1, 2006. For new
legally required standby systems that are supplied from an
existing legally required standby system installed prior to
June 1, 2006, the new portion of the legally required standby
system must comply with NEC 701.18. The ground fault sensing
function of overcurrent protective devices will only be
required to selectively coordinate with the ground fault
sensing functions of other overcurrent protective devices.
[Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031,
19.28.041, 19.28.061, 19.28.101, 19.28.131, 19.28.161,
19.28.171, 19.28.191, 19.28.201, 19.28.211, 19.28.241,
19.28.251, 19.28.281, 19.28.311, 19.28.321, 19.28.400,
19.28.420, 19.28.490, 19.28.551. 08-24-048, § 296-46B-701,
filed 11/25/08, effective 12/31/08; 06-24-041, § 296-46B-701,
filed 11/30/06, effective 12/31/06.]