WAC 296-46B-690
Solar photovoltaic systems.
002 Definitions.
(1) Photovoltaic system. The photovoltaic system may
conduct alternating current, direct current, or both and will
comprise all interconnected circuits to the point of
connection with the building distribution circuits or utility
service conductors.
(2) Support structure, foundation, and tracker. For the
purposes of this section, those portions of the array or
tracker that are exclusively mechanical and are built
specifically for the purpose of physically supporting the
modules or panels will not be considered part of the
photovoltaic system as defined by this article.
004 Installation.
(3) A photovoltaic system design review must be submitted
at the time of the first inspection. The design review must
be available to the inspector on the job site. Permit holders
must submit, to the electrical authority having jurisdiction,
copies of the photovoltaic equipment manufacturer's
installation information, accompanied by a legible one-line
diagram of the photovoltaic design and calculations used to
determine voltage and current within the photovoltaic system. This diagram must show the photovoltaic equipment, devices,
overcurrent protection, conductor sizing, grounding, ground
fault protection if required, and any system interconnection
points.
(4) For utility interactive systems, persons making
interconnections between solar photovoltaic system and the
utility distribution network must consult the serving utility
and are required to meet all additional utility standards.
007 Maximum voltage.
(5) The open-circuit voltage temperature coefficients
supplied in the instructions of listed photovoltaic modules
will be used to determine the maximum direct current
photovoltaic system voltage. Otherwise the voltage will be
calculated using Table 690.7 of the NEC. For the purposes of
this calculation, a temperature correction factor of 1.25 will
be used unless another factor can be justified and is approved
by the authority having jurisdiction.
053 Direct-current photovoltaic power source.
(6) All photovoltaic equipment and disconnecting means
must be permanently identified as to their purpose, maximum
voltages, and type of current within the system with an
identification plate. All photovoltaic circuits must be
identified at each overcurrent protection device(s) and panel
directory(ies).
(7) Required "WARNING" labels as specified by NEC 690 are
required to be an identification plate on or immediately
adjacent to the pertinent equipment.
[Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031,
19.28.041, 19.28.061, 19.28.101, 19.28.131, 19.28.161,
19.28.171, 19.28.191, 19.28.201, 19.28.211, 19.28.241,
19.28.251, 19.28.281, 19.28.311, 19.28.321, 19.28.400,
19.28.420, 19.28.490, 19.28.551. 09-20-032, § 296-46B-690,
filed 9/29/09, effective 10/31/09; 08-24-048, § 296-46B-690,
filed 11/25/08, effective 12/31/08.]