WAC 296-46B-680
Special equipment -- Swimming pools,
fountains and similar installations.
001 General.
(1) Package spa or hot tubs. Electrical heating,
pumping, filtering, and/or control equipment installed within
five feet of a spa or hot tub must be listed or field
evaluated as a package with the spa or hot tub.
(2) A factory assembled skid pack of electrical heating,
pumping, filtering, and/or control equipment (skid pack) must
be installed more than five feet from a spa or hot tub and
shall be listed as a package unit.
(3) The maintenance disconnect and field installed,
listed electrical equipment for a hot tub, spa, or swim spa
must be located at least five feet from the hot tub, spa or
swim spa. Field installed listed equipment must meet the
following additional requirements:
(a) The heater is listed as a "spa heater or swimming
pool heater";
(b) The pump is listed as a "spa pump" or "swimming
pool/spa pump" (the pump may be combined with a filter
assembly); and
(c) Other listed equipment such as panelboards, conduit,
and wire are suitable for the environment and comply with the
applicable codes.
(4) Field installed, listed electrical equipment for a
swimming pool must be located at least five feet from the
swimming pool. Field installed listed equipment must meet the
following additional requirements:
(a) The heater must be listed as a "swimming pool heater
or a spa heater";
(b) The pump must be listed as a "swimming pool pump" or
"spa pump" or "swimming pool/spa pump"; and
(c) Other equipment such as panelboards, conduit, and
wire must be suitable for the environment and comply with the
applicable codes.
The five-foot separation may be reduced by the
installation of a permanent barrier, such as a solid wall,
fixed glass windows or doors, etc. The five-foot separation
will be determined by the shortest path or route that a cord
can travel from the spa, hot tub, swim spa, or swimming pool
to an object.
(5) The field assembly or installation of "recognized
components" will not be permitted.
(6) Hydromassage bathtubs must be listed as a unit and
bear a listing mark which reads "hydromassage bathtub."
(7) Manufacturers' instructions must be followed as part
of the listing requirements.
(8) Electrical components which have failed and require
replacement must be replaced with identical products unless
the replacement part is no longer available; in which case, a
like-in-kind product may be substituted provided the
mechanical and grounding integrity of the equipment is
maintained.
(9) Cut-away-type display models may not be sold for
other than display purposes and are not expected to bear a
listing mark.
025 Feeders.
(10) NEC 680.25(A) is amended to read: A feeder between
the service equipment and the remote panelboard is permitted
to run in flexible metal conduit, an approved cable assembly
that includes an equipment grounding conductor within its
outer sheath (the equipment grounding conductor must comply
with NEC 250.24 (A)(5)), rigid metal conduit, intermediate
metal conduit, liquidtight flexible nonmetallic conduit, rigid
polyvinyl chloride conduit, reinforced thermosetting resin
conduit, electrical metallic tubing (when installed on or
within a building or crawl space), and electrical nonmetallic
tubing (when installed within a building or crawl space).
Aluminum conduit is not permitted.
040 Spas and hot tubs.
(11) NEC 680.42(C) will apply for interior and exterior
wiring to outdoor installations of spas and hot tubs.
[Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031,
19.28.041, 19.28.061, 19.28.101, 19.28.131, 19.28.161,
19.28.171, 19.28.191, 19.28.201, 19.28.211, 19.28.241,
19.28.251, 19.28.281, 19.28.311, 19.28.321, 19.28.400,
19.28.420, 19.28.490, 19.28.551. 08-24-048, § 296-46B-680,
filed 11/25/08, effective 12/31/08. Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031, 19.28.041, 19.28.061,
19.28.101, 19.28.131, 19.28.161, 19.28.171, 19.28.191,
19.28.201, 19.28.211, 19.28.241, 19.28.251, 19.28.271,
19.28.311, 19.28.321, 19.28.400, 19.28.420, 19.28.490,
19.28.551, 2002 c 249, chapters 34.05 and 19.28 RCW. 03-09-111, § 296-46B-680, filed 4/22/03, effective 5/23/03.]