WAC 296-46B-555
Special occupancies -- Marinas and
boatyards. (1) For the purposes of NEC 555.1, the scope of
work includes private, noncommercial docking facilities.
(2) For the purposes of NEC 555.5, transformer
terminations must be located a minimum of twelve inches above
the deck of a dock (datum plane requirements do not apply for
this section).
(3) For the purposes of NEC 555.7, adjacent means within
sight.
(4) For the purposes of NEC 555.9, all electrical
connections must be installed a minimum of twelve inches above
the deck of a pier unless the connections are approved for wet
locations (datum plane requirements do not apply for this
section).
(5) For the purposes of NEC 555.10, all enclosures must
be corrosion resistant. All gasketed enclosures must be
arranged with a weep hole to discharge condensation.
(6) For the purposes of NEC 555.11, gasketed enclosures
are only required for wet locations.
(7) For the purposes of NEC 555.13, the following wiring
methods are allowed:
(a) All wiring installed in a damp or wet location must
be suitable for wet locations.
(b) Extra-hard usage portable power cables rated not less
than 75°C, 600 volts, listed for wet locations and sunlight
resistance and having an outer jacket rated for the
environment are permitted. Portable power cables are
permitted as a permanent wiring method under or within docks
and piers or where provided with physical protection. The
requirements of NEC 555.13 (B)(4)(b) do not apply.
(c) Overhead wiring must be installed at the perimeter of
areas where boats are moored, stored, moved, or serviced to
avoid possible contact with masts and other parts of boats.
(d) For the purposes of NEC 555.13 (B)(5), the wiring
methods of Chapter 3 NEC will be permitted.
(8) For the purposes of NEC 555.19, receptacles must be
mounted not less than twelve inches above the deck surface of
the pier or dock (datum plane requirements do not apply for
this section). Shore power receptacles that provide shore
power for boats must be rated not less than 20 amperes and
must be single outlet type and must be of the locking and
grounding type or pin and sleeve type.
(9) For the purposes of NEC 555.21 (B)(1), delete exception
No. 1 and No. 2 and replace with:
Dock, pier, or wharf sections that do not support fuel
dispensers and may abut a section(s) that supports a fuel
dispenser(s) are permitted to be unclassified where documented
air space between the sections is provided and where flammable
liquids or vapors cannot travel to these sections. See NEC
500.4(A) for documentation requirements.
[Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031,
19.28.041, 19.28.061, 19.28.101, 19.28.131, 19.28.161,
19.28.171, 19.28.191, 19.28.201, 19.28.211, 19.28.241,
19.28.251, 19.28.281, 19.28.311, 19.28.321, 19.28.400,
19.28.420, 19.28.490, 19.28.551. 08-24-048, § 296-46B-555,
filed 11/25/08, effective 12/31/08; 06-05-028, § 296-46B-555,
filed 2/7/06, effective 5/1/06. Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031, 19.28.041, 19.28.061,
19.28.101, 19.28.131, 19.28.161, 19.28.171, 19.28.191,
19.28.201, 19.28.211, 19.28.241, 19.28.251, 19.28.271,
19.28.311, 19.28.321, 19.28.400, 19.28.420, 19.28.490,
19.28.551, 2002 c 249, chapters 34.05 and 19.28 RCW. 03-09-111, § 296-46B-555, filed 4/22/03, effective 5/23/03.]