WAC 296-46B-553
Special occupancies -- Floating buildings.
004 Floating buildings and similar facilities - services
and feeders.
(1) Where electrical power is provided, floating
buildings and similar facilities in addition to complying with
the appropriate sections of Article 553 NEC must have a
readily accessible service rated disconnect located on the
shoreline within sight of the shoreline connection of the
dock, wharf or similar structure to which the floating
building or similar facility is moored.
(2) Where shore power is provided, each floating building
or similar facility must have a disconnecting means located
within sight of each floating building or similar facility.
The disconnecting means must be installed adjacent to but not
in or on the floating building or similar facility.
007 Floating buildings and similar installations - wiring
methods.
(3) Extra-hard usage portable power cables rated not less
than 75°C, 600 volts, listed for wet locations and sunlight
resistance and having an outer jacket rated for the
environment may be used as a permanent wiring method when
joining the structures indicated above and for any concealed
or protected wiring on a sectionalized floating dock leading
to a floating building or similar facility. The cable needs
to be resistant only to environments it is normally exposed to
on an ongoing basis.
(4) Conductors operating in excess of 600 volts, nominal
may not be installed on floating portions of a floating
building or similar facility.