WAC 296-46B-358
Wiring methods and materials -- Electrical
metallic tubing.
012 Electrical metallic tubing.
(1) In addition to complying with the provisions of
Article 358 NEC, electrical metallic tubing may not be
installed in direct contact with the earth or in concrete on
or below grade. Also see NEC 300.6 for resistance to
corrosion.
(2) Where electrical metallic tubing is installed in wet
locations, an equipment grounding conductor must be provided
within the raceway and sized per NEC 250.122.