WAC 296-46B-334
Wiring methods and
materials -- Nonmetallic-sheathed cable.
010 Nonmetallic-sheathed cable.
(1) The building classification, for subsections (2),
(3), and (4) of this section, will be as determined by the
building official. For the purposes of this section, Type
III, IV and V may be as defined in the International Building
Code adopted in the state of Washington. The installer must
provide the inspector documentation substantiating the type of
building construction and finish material rating(s) prior to
any electrical inspection.
(2) This section replaces NEC 334.10(2). In multifamily
dwellings, Type NM, Type NMC, and Type NMS cable(s) may be
used in structures of Types III, IV, and V construction except
as prohibited in NEC 334.12.
(3) This section replaces NEC 334.10(3). In all other
structures, Type NM, Type NMC, and Type NMS cable(s) may be
used in structures of Types III, IV, and V construction except
as prohibited in NEC 334.12. All cable(s) must be concealed
within walls, floors, or ceilings that provide a thermal
barrier of material that has at least a 15-minute finish
rating as identified in listings of fire-rated assemblies.
(4) This section replaces NEC 334.10(4). Cable trays in
structures of Types III, IV, and V construction, where the
cable(s) is identified for the use, except as prohibited in
NEC 334.12.
015 Exposed work.
(5) Where Type NMC cable is installed in shallow chases
in plaster, masonry, concrete, adobe or similar material, the
cable must be protected against nails or screws by:
(a) A steel plate at least 1.59 mm (1/16 in.) thick and
covered with plaster, adobe, or similar finish; or
(b) Being recessed in a chase at least 6.985 cm (2 3/4
in.) deep, as measured from the finished surface, and covered
with plaster, adobe, or similar finish. The cable(s) must be
at least 6.35 mm (2 1/2 in.) from the finished surface.
(6) The requirements for nonmetallic sheathed cable
protection in NEC 334.15(C) do not apply in crawl spaces.
[Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031,
19.28.041, 19.28.061, 19.28.101, 19.28.131, 19.28.161,
19.28.171, 19.28.191, 19.28.201, 19.28.211, 19.28.241,
19.28.251, 19.28.281, 19.28.311, 19.28.321, 19.28.400,
19.28.420, 19.28.490, 19.28.551. 08-24-048, § 296-46B-334,
filed 11/25/08, effective 12/31/08; 05-10-024, § 296-46B-334,
filed 4/26/05, effective 6/30/05. Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031, 19.28.041, 19.28.061,
19.28.101, 19.28.131, 19.28.161, 19.28.171, 19.28.191,
19.28.201, 19.28.211, 19.28.241, 19.28.251, 19.28.271,
19.28.311, 19.28.321, 19.28.400, 19.28.420, 19.28.490,
19.28.551, 2003 c 399, 2003 c 211, 2003 c 78, and 2003 c 242. 04-12-049, § 296-46B-334, filed 5/28/04, effective 6/30/04. Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031,
19.28.041, 19.28.061, 19.28.101, 19.28.131, 19.28.161,
19.28.171, 19.28.191, 19.28.201, 19.28.211, 19.28.241,
19.28.251, 19.28.271, 19.28.311, 19.28.321, 19.28.400,
19.28.420, 19.28.490, 19.28.551, 2002 c 249, chapters 34.05 and 19.28 RCW. 03-09-111, § 296-46B-334, filed 4/22/03,
effective 5/23/03.]