WAC 296-46B-300
Wiring methods and materials -- Wiring
methods.
001 Wiring methods.
(1) Cables and raceways for telecommunications, power
limited, NEC Class 2 and Class 3 conductors must be installed
in compliance with Chapter 3 NEC unless other methods are
specifically allowed or required elsewhere in the NEC, chapter 19.28 RCW, or this chapter.
005 Underground installations.
(2) Induction loops.
See WAC 296-46B-010(17) for induction
detection loops that are made in a public roadway and
regulated by a governmental agency.
Other induction loops must comply with the following
requirements:
(a) General:
(i) A preformed direct burial induction loop is designed
to be installed within the road surface base (e.g., concrete
or asphalt) or below the road surface of a road with an
unpaved surface (e.g., gravel or brick pavers);
(ii) A saw-cut induction detection loop is designed to be
installed into a groove saw-cut into an existing paved road
surface (e.g., concrete or asphalt);
(iii) The loop system includes the loop and the lead-in
conductor;
(iv) The loop system must be:
(A) Tested to assure that at 500 volts DC, the resistance
between the conductor and ground equals or exceeds 50 megohms;
and
(B) Without splice; or
(C) If spliced, the splice must be soldered and
appropriately insulated;
(v) The lead-in conductor must comply with the following:
(A) Must be stranded and have a lay (i.e., twist) of two
turns per foot; and
(B) If installed in an electrical raceway;
• Are not required to be listed or suitable for wet
locations; and
• Must have a burial cover of at least 6"; or
(C) If direct buried;
• Must be listed for the use; and
• Must have a burial cover of at least 18".
(b) Preformed direct burial induction detection loops
must conform with the following:
(i) The loop conductor must be rated for direct burial
and be a minimum of No. 16 AWG;
(ii) The loop design must not allow movement of the loop
conductor within the outer jacket. The outer jacket
containing the loop conductor is not required to be listed;
(iii) The loop yoke casing (i.e., the location where the
lead-in conductor is connected to the loop):
(A) Includes any device used to house the "loop to
lead-in splice" or to otherwise couple the loop with the
lead-in electrical raceway;
(B) Is not required to be listed; and
(C) Must have a coupler that will create a waterproof
bond with the electrical raceway, containing the lead-in
conductor, or a direct buried lead-in conductor.
(c) Saw-cut induction detection loops:
(i) The loop conductor must be cross-linked polyethylene
or EPR Type USE insulation and be a minimum of No. 18 AWG
stranded;
(ii) The saw-cut groove must not cut into rebar installed
within the roadway.
011 Support of raceways, cables, or boxes in suspended
ceilings.
(3) NEC power limited, Class 2, and Class 3 cables must
be secured in compliance with NEC 334.30 and must be secured
to boxes in compliance with NEC 314.17.
(4) Telecommunications cables must be secured in a manner
that will not cause damage to the cables and at intervals not
exceeding five feet. Cables are considered adequately
supported when run through holes in building structural
elements or other supporting elements. Telecommunications
cables may be fished into inaccessible hollow spaces of
finished buildings. Clamps or fittings are not required where
telecommunications cables enter boxes.
(5) Optical fiber cables must be secured in a manner that
will not cause damage to the cables and at intervals not
exceeding five feet. Cables are considered adequately
supported when run through holes in building structural
elements or other supporting elements. Optical fiber cables
may be fished into inaccessible hollow spaces of finished
buildings. Supports must allow a bending radius that will not
cause damage to the cables.
(6) Where not restricted by the building code official or
Article 300 NEC, the wires required in NEC 300.11(A) may
support raceways, cables, or boxes under the following
conditions:
(a) Raceways and/or cables are not larger than
three-quarter-inch trade size;
(b) No more than two raceways or cables are supported by
a support wire. The two-cable limitation does not apply to
telecommunications cables, Class 2 cables, or Class 3 cables
on support wires installed exclusively for such cables. The
support wire must be adequate to carry the cable(s) weight and
all attached cables must be secured with approved fittings; or
(c) Raceways and cables are secured to the support wires
by fittings designed and manufactured for the purpose.
In addition to (a), (b), and (c) of this subsection, the
following conditions must be complied with:
(d) The support wires are minimum #12 AWG and are
securely fastened to the structural ceiling and to the ceiling
grid system; and
(e) The raceways or cables serve equipment that is
located within the ceiling cavity or is mounted on or
supported by the ceiling grid system. Telecommunications
cables, Class 2 cables, or Class 3 cables supported as
required by this section, may pass through ceiling cavities
without serving equipment mounted on or supported by the
ceiling grid system.
017 Conductors in raceway.
(7) Cables will be permitted in all raceway systems if:
(a) The cable is appropriate for the environment; and
(b) The percentage fill does not exceed that allowed in
NEC Chapter 9, Table 1.
[Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031,
19.28.041, 19.28.061, 19.28.101, 19.28.131, 19.28.161,
19.28.171, 19.28.191, 19.28.201, 19.28.211, 19.28.241,
19.28.251, 19.28.281, 19.28.311, 19.28.321, 19.28.400,
19.28.420, 19.28.490, 19.28.551. 08-24-048, § 296-46B-300,
filed 11/25/08, effective 12/31/08; 06-24-041, § 296-46B-300,
filed 11/30/06, effective 12/31/06; 05-10-024, § 296-46B-300,
filed 4/26/05, effective 6/30/05. Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031, 19.28.041, 19.28.061,
19.28.101, 19.28.131, 19.28.161, 19.28.171, 19.28.191,
19.28.201, 19.28.211, 19.28.241, 19.28.251, 19.28.271,
19.28.311, 19.28.321, 19.28.400, 19.28.420, 19.28.490,
19.28.551, 2003 c 399, 2003 c 211, 2003 c 78, and 2003 c 242. 04-12-049, § 296-46B-300, filed 5/28/04, effective 6/30/04. Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031,
19.28.041, 19.28.061, 19.28.101, 19.28.131, 19.28.161,
19.28.171, 19.28.191, 19.28.201, 19.28.211, 19.28.241,
19.28.251, 19.28.271, 19.28.311, 19.28.321, 19.28.400,
19.28.420, 19.28.490, 19.28.551, 2002 c 249, chapters 34.05 and 19.28 RCW. 03-09-111, § 296-46B-300, filed 4/22/03,
effective 5/23/03.]