WAC 296-46B-110
General -- Requirements for electrical
installations.
003 Examination, identification, installation, and use of
equipment.
(1) Listed electrical conduit can only be installed and
used in accordance with its listing (i.e., as an electrical
raceway for electrical conductors). If used as a sleeve for
electrical conductors or other listed electrical conduits, the
installation of a listed electrical conduit will be assumed to
be for use as an electrical raceway and must be installed as
allowed by chapter 19.28 RCW and this chapter (e.g., owner
exemption, electrical contractor, etc.).
011 Deteriorating agents.
(2) Electrical equipment and wiring that has been
submerged or exposed to water must comply with the following:
(a) All breakers, fuses, controllers, receptacles,
lighting switches/dimmers, electric heaters, and any sealed
device/equipment (e.g., relays, contactors, etc.) must be
replaced.
(b) All other electrical equipment (e.g., wiring, breaker
panelboards, disconnect switches, switchgear, motor control
centers, boiler controls, HVAC/R equipment, electric motors,
transformers, appliances, water heaters, and similar
appliances) must be replaced or reconditioned by the original
manufacturer or by its approved representative.
016 Flash protection.
(3) The flash protection marking required by NEC 110.16
must be an identification plate or label approved by the
electrical inspector and may be installed either in the field
or in the factory. The plate or label may be mounted using
adhesive.
022 Identification of disconnecting means.
(4) For the purposes of legibly marking a disconnecting
means, as required in NEC 110.22, an identification plate is
required unless the disconnect is a circuit breaker/fused
switch installed within a panelboard and the circuit
breaker/fused switch is identified by a panelboard schedule. In other than dwelling units, the identification plate must
include the identification designation of the circuit source
panelboard that supplies the disconnect.
030 Over 600 volts - general.
(5) Each cable operating at over 600 volts and installed
on customer-owned systems must be legibly marked in a
permanent manner at each termination point and at each point
the cable is accessible. The required marking must use phase
designation, operating voltage, and circuit number if
applicable.
[Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031,
19.28.041, 19.28.061, 19.28.101, 19.28.131, 19.28.161,
19.28.171, 19.28.191, 19.28.201, 19.28.211, 19.28.241,
19.28.251, 19.28.281, 19.28.311, 19.28.321, 19.28.400,
19.28.420, 19.28.490, 19.28.551. 08-24-048, § 296-46B-110,
filed 11/25/08, effective 12/31/08; 06-24-041, § 296-46B-110,
filed 11/30/06, effective 12/31/06; 06-05-028, § 296-46B-110,
filed 2/7/06, effective 5/1/06; 05-22-025, § 296-46B-110,
filed 10/25/05, effective 11/25/05; 05-10-024, § 296-46B-110,
filed 4/26/05, effective 6/30/05. Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031, 19.28.041, 19.28.061,
19.28.101, 19.28.131, 19.28.161, 19.28.171, 19.28.191,
19.28.201, 19.28.211, 19.28.241, 19.28.251, 19.28.271,
19.28.311, 19.28.321, 19.28.400, 19.28.420, 19.28.490,
19.28.551, 2003 c 399, 2003 c 211, 2003 c 78, and 2003 c 242. 04-12-049, § 296-46B-110, filed 5/28/04, effective 6/30/04. Statutory Authority: RCW 19.28.006, 19.28.010, 19.28.031,
19.28.041, 19.28.061, 19.28.101, 19.28.131, 19.28.161,
19.28.171, 19.28.191, 19.28.201, 19.28.211, 19.28.241,
19.28.251, 19.28.271, 19.28.311, 19.28.321, 19.28.400,
19.28.420, 19.28.490, 19.28.551, 2002 c 249, chapters 34.05 and 19.28 RCW. 03-09-111, § 296-46B-110, filed 4/22/03,
effective 5/23/03.]