WAC 296-45-225
Underground residential distribution
(URD). (1) General.
(a) Each employee shall be knowledgeable of the equipment
provided for their use and shall at all times use this
equipment only for the purpose intended.
(b) U.R.D. cables which are properly insulated for the
voltages to which they are energized shall be considered as an
effective barrier to protect the employees and table one need
not apply.
(i) Workers will take adequate precautions to avoid
physical contact with energized U.R.D. cable by using approved
procedures and/or protective devices.
(ii) When handling energized U.R.D. primary cables, the
work shall be done with approved tools and/or procedures by
two qualified employees. Switching is exempt from this rule.
(iii) When energized terminators or load-break elbows are
handled by a hot stick, there shall be two qualified employees
at the scene.
(c) When energized pad-mounted transformers or similar
equipment are to be left unlocked and open, they shall be
attended by a qualified employee.
(d) Approved tools and procedures shall be used to remove
any debris, vines, weeds, etc., from an underground system.
(e) A primary and secondary system neutral on any
energized circuit shall not be opened under any circumstances
except for testing.
(f) Primary and secondary neutrals shall be firmly
connected and grounded before the circuit or equipment is
energized.
(g) Where different phases are in the same vault,
enclosures, or parked in some manner that they could be
looped, these phases shall be marked or identified.
(h) Bayonet fuses:
(i) Bayonet fuses shall not be closed into suspected
faults or overloads.
(ii) Submersible U.G. transformer installations will
require other methods of energizing or de-energizing and
bayonet fuses shall not be used for this purpose.
(iii) Bayonet fuses shall only be operated after
pad-mount transformers have been properly vented.
(iv) Bayonet fuses shall only be operated in accordance
with manufacturing design and rating capabilities.
(2) Working on cables.
(a) Before any work is to be performed on underground
cables and apparatus carrying high voltage, they shall be
deenergized with the following exceptions:
(i) Replacing fuses, operating switches, closing or
opening load-break elbows, when approved protective devices
are used.
(ii) Work in the high-voltage compartment of pad-mounted
transformers and similar equipment installed above ground,
provided the work is done by approved methods.
(b) Only one energized conductor shall be worked on at
any one time, and protective means shall be used to insulate
or isolate it from all others.
(c) When work is to be performed in manholes containing
any wires or appliances carrying electrical current, they
shall be in a sanitary condition.
[Statutory Authority: RCW 49.17.010, [49.17].040, [49.17].050
and [49.17].060. 98-07-009, § 296-45-225, filed 3/6/98,
effective 5/6/98.]