WAC 296-45-17565
Central system operator. If energy
isolating devices are installed in a central location under the
exclusive control of a system operator, the following
requirements apply:
(1) The employer shall use a procedure that affords
employees a level of protection equivalent to that provided by
the implementation of a personal lockout or tagout device.
(2) The system operator shall place and remove lockout and
tagout devices in place of the authorized employee.
(3) Provisions shall be made to identify the authorized
employee who is responsible for (that is, being protected by) the
lockout or tagout device, to transfer responsibility for lockout
and tagout devices, and to ensure that an authorized employee
requesting removal or transfer of a lockout or tagout device is
the one responsible for it before the device is removed or
transferred.
[Statutory Authority: RCW 49.17.010, [49.17].040, [49.17].050
and [49.17].060. 98-07-009, § 296-45-17565, filed 3/6/98,
effective 5/6/98.]