| APPROACH DISTANCES TO EXPOSED ENERGIZED OVERHEAD POWER LINES AND PARTS |
|||
| Voltage Range (phase to phase, RMS) |
Approach Distance (inches) |
||
| 300 V and less —————————————————— | (1) | ||
| Over 300 V, not over 750 V —————————————— | 12 | ||
| Over 750 V not over 2 kV ——————————————– | 18 | ||
| Over 2 kV, not over 15 kV —–————————————— | 24 | ||
| Over 15 kV, not over 37 kV —————————————— | 36 | ||
| Over 37 kV, not over 87.5 kV ————————————— | 42 | ||
| Over 87.5 kV, not over 121 kV ————————————– | 48 | ||
| Over 121 kV, not over 140 kV ————————————— | 54 | ||
(1)Avoid contact. |
|||