| Note: | Personal protective equipment requirements are contained in chapter 296-24 WAC Part L, and WAC 296-800-160. |
| Note: | Rubber insulating equipment meeting the following national consensus standards is deemed to be in compliance with subsection (1) of this section: |
| American Society for Testing and Materials (ASTM) D 120-87, Specification for Rubber Insulating Gloves. |
| ASTM D 178-93, Specification for Rubber Insulating Matting. |
| ASTM D 1048-93, Specification for Rubber Insulating Blankets. |
| ASTM D 1049-93, Specification for Rubber Insulating Covers. |
| ASTM D 1050-90, Specification for Rubber Insulating Line Hose. |
| ASTM D 1051-87, Specification for Rubber Insulating Sleeves. |
| These standards contain specifications for conducting the various tests required in subsection (1) of this section. For example, the a-c and d-c proof-tests, the breakdown test, the water soak procedure, and the ozone test mentioned in this paragraph are described in detail in the ASTM standards. |
| Note: | Standard electrical test methods considered as meeting this requirement are given in the following national consensus standards: |
| American Society for Testing and Materials (ASTM) D 120-87, Specification for Rubber Insulating Gloves. |
| ASTM D 1048-93, Specification for Rubber Insulating Blankets. |
| ASTM D 1049-93, Specification for Rubber Insulating Covers. |
| ASTM D 1050-90, Specification for Rubber Insulating Line Hose. |
| ASTM D 1051-87, Specification for Rubber Insulating Sleeves. |
| ASTM F 478-92, Specification for In-Service Care of Insulating Line Hose and Covers. |
| ASTM F 479-88a, Specification for In-Service Care of Insulating Blankets. |
| ASTM F 496-93b, Specification for In-Service Care of Insulating Gloves and Sleeves. |
| Note: | Marking of equipment and entering the results of the tests and the dates of testing onto logs are two acceptable means of meeting this requirement. |
| Table A-2. -A-C Proof-Test Requirements Maximum proof-test current, mA (gloves only) | Proof-test voltage rms V | 267-mm (10.5-in) glove | 356-mm (14-in) glove | 406-mm (16-in) glove | 457-mm (18-in) glove | |
| Class of equipment | ||||||
| 0 | 5,000 | 8 | 12 | 14 | 16 | |
| 1 | 10,000 | 14 | 16 | 18 | ||
| 2 | 20,000 | 16 | 18 | 20 | ||
| 3 | 30,000 | 18 | 20 | 22 | ||
| 4 | 40,000 | 22 | 24 | |||
| Table A-3. -D-C Proof-Test Requirements | Class of equipment | Proof-test voltage |
| 0 | 20,000 | |
| 1 | 40,000 | |
| 2 | 50,000 | |
| 3 | 60,000 | |
| 4 | 70,000 |
| Note: | The d-c voltages listed in this table are not appropriate for proof-testing rubber insulating line hose or covers. For this equipment, d-c proof-tests shall use a voltage high enough to indicate that the equipment can be safely used at the voltages listed in Table A-4. See ASTM D 1050-90 and ASTM D 1049-88 for further information on proof-tests for rubber insulating line hose and covers. |
| Table A-4. -Glove Tests-Water Level1, 2 Class of glove |
mm. | A-C proof-test in. | mm. | D-C proof-test in. |
| 0 | 38 | 1.5 | 38 | 1.5 |
| 1 | 38 | 1.5 | 51 | 2.0 |
| 2 | 64 | 2.5 | 76 | 3.0 |
| 3 | 89 | 3.5 | 102 | 4.0 |
| 4 | 127 | 5.0 | 153 | 6.0 |
| 1 | The water level is given as the clearance from the cuff of the glove to the water line, with a tolerance of 13 mm. (0.5 in.). |
| 2 | If atmospheric conditions make the specified clearances impractical, the clearances may be increased by a maximum of 25 mm. (1 in.). |
| Table A-5. -Rubber
Insulating
Equipment Voltage
Requirements Class of equipment |
Maximum use voltage1 a-c-rms | Retest voltage2 a-c-rms | Retest voltage2 d-c-rms |
| 0 | 1,000 | 5,000 | 20,000 |
| 1 | 7,500 | 10,000 | 40,000 |
| 2 | 17,000 | 20,000 | 50,000 |
| 3 | 26,500 | 30,000 | 60,000 |
| 4 | 36,000 | 40,000 | 70,000 |
| Note: | Rubber gloves shall only be used on voltages of 5000 volts phase-to-phase or less. |
| 1The maximum use voltage is the a-c voltage (rms) classification of the protective equipment that designates the maximum nominal design/voltage of the energized system that may be safely worked. The nominal design voltage is equal to the phase-to-phase voltage on multiphase circuits. However, the phase-to-ground potential is considered to be the nominal design/voltage: | |
| 1. If there is no multiphase exposure in a system area and if the voltage exposure is limited to the phase-to-ground potential, or | |
| 2. If the electrical equipment and devices are insulated or isolated or both so that the multiphase exposure on a grounded wye circuit is removed. | |
| 2 The proof-test voltage shall be applied continuously for at least one minute, but no more than three minutes. |
| Table A-6. -Rubber Insulating Equipment Test Intervals | Type of equipment | When to test |
| Rubber insulating line hose | Upon indication that insulating value is suspect. | |
| Rubber insulating covers | Upon indication that insulating value is suspect. | |
| Rubber insulating blankets | Before first issue and every 12 months thereafter.1 | |
| Rubber insulating gloves | Before first issue and every 6 months thereafter.1 | |
| Rubber insulating sleeves | Before first issue and every 12 months thereafter.1 |
| 1 | If the insulating equipment has been electrically tested but not issued for service, it may not be placed into service unless it has been electrically tested within the previous 12 months. |