WAC 296-24-59215
Appendix A -- Portable fire
extinguishers. (1) Scope and application. The scope and
application of this section is written to apply to three basic
types of workplaces. First, there are those workplaces where
the employer has chosen to evacuate all employees from the
workplace at the time of a fire emergency. Second, there are
those workplaces where the employer has chosen to permit
certain employees to fight fires and to evacuate all other
nonessential employees at the time of a fire emergency. Third, there are those workplaces where the employer has
chosen to permit all employees in the workplace to use
portable fire extinguishers to fight fires.
The section also addresses two kinds of work areas. The
entire workplace can be divided into outside (exterior) work
areas and inside (interior) work areas. This division of the
workplace into two areas is done in recognition of the
different types of hazards employees may be exposed to during
firefighting operations. Fires in interior workplaces, pose a
greater hazard to employees; they can produce greater exposure
to quantities of smoke, toxic gases, and heat because of the
capability of a building or structure to contain or entrap
these products of combustion until the building can be
ventilated. Exterior work areas, normally open to the
environment, are somewhat less hazardous, because the products
of combustion are generally carried away by the thermal column
of the fire. Employees also have a greater selection of
evacuation routes if it is necessary to abandon firefighting
efforts.
In recognition of the degree of hazard present in the two
types of work areas, the standards for exterior work areas are
somewhat less restrictive in regards to extinguisher
distribution. WAC 296-800-300 explains this by specifying
which sections apply.
(2) Portable fire extinguisher exemptions. In
recognition of the three options given to employers in regard
to the amount of employee evacuation to be carried out, the
standards permit certain exemptions based on the number of
employees expected to use fire extinguishers.
Where the employer has chosen to totally evacuate the
workplace at the time of a fire emergency and when fire
extinguishers are not provided, the requirements of this
section do not apply to that workplace.
Where the employer has chosen to partially evacuate the
workplace or the effected area at the time of a fire emergency
and has permitted certain designated employees to remain
behind to operate critical plant operations or to fight fires
with extinguishers, then the employer is exempt from the
distribution requirements of this section. Employees who will
be remaining behind to perform incipient firefighting or
members of a fire brigade must be trained in their duties. The training must result in the employees becoming familiar
with the locations of fire extinguishers. Therefore, the
employer must locate the extinguishers in convenient locations
where the employees know they can be found. For example, they
could be mounted in the fire truck or cart that the fire
brigade uses when it responds to a fire emergency. They can
also be distributed as set forth in the National Fire
Protection Association's Standard No. 10, "Portable Fire
Extinguishers."
Where the employer has decided to permit all employees in
the workplace to use fire extinguishers, then the entire WISHA
standard applies.
(3) Portable fire extinguisher mounting. Previous
standards for mounting fire extinguishers have been criticized
for requiring specific mounting locations. In recognition of
this criticism, the standard has been rewritten to permit as
much flexibility in extinguisher mounting as is acceptable to
assure that fire extinguishers are available when needed and
that employees are not subjected to injury hazards when they
try to obtain an extinguisher.
It is the intent of WISHA to permit the mounting of
extinguishers in any location that is accessible to employees
without the use of portable devices such as a ladder. This
limitation is necessary because portable devices can be moved
or taken from the place where they are needed and, therefore,
might not be available at the time of an emergency.
Employers are given as much flexibility as possible to
assure that employees can obtain extinguishers as fast as
possible. For example, an acceptable method of mounting
extinguishers in areas where fork lift trucks or tow-motors
are used is to mount the units on retractable board which, by
means of counterweighting, can be raised above the level where
they could be struck by vehicular traffic. When needed, they
can be lowered quickly for use. This method of mounting can
also reduce vandalism and unauthorized use of extinguishers. The extinguishers may also be mounted as outlined in the
National Fire Protection Association's Standard No. 10,
"Portable Fire Extinguishers."
(4) Selection and distribution. The employer is
responsible for the proper selection and distribution of fire
extinguishers and the determination of the necessary degree of
protection. The selection and distribution of fire
extinguishers must reflect the type and class of fire hazards
associated with a particular workplace.
Extinguishers for protecting Class A hazards may be
selected from the following types: Water, foam, loaded
stream, or multipurpose dry chemical. Extinguishers for
protecting Class B hazards may be selected from the following
types: Halon 1301, Halon 1211, carbon dioxide, dry chemicals,
foam, or loaded stream. Extinguishers for Class C hazards may
be selected from the following types: Halon 1301, Halon 1211,
carbon dioxide, or dry chemical.
Combustible metal (Class D hazards) fires pose a
different type of fire problem in the workplace. Extinguishers using water, gas, or certain dry chemicals
cannot extinguish or control this type of fire. Therefore,
certain metals have specific dry powder extinguishing agents
which can extinguish or control this type of fire. Those
agents which have been specifically approved for use on
certain metal fires provide the best protection; however,
there are also some "universal" type agents which can be used
effectively on a variety of combustible metal fires if
necessary. The "universal" type agents include: Foundry
flux, Lith-X powder, TMB liquid, pyromet powder, TEC powder,
dry talc, dry graphite powder, dry sand, dry sodium chloride,
dry soda ash, lithium chloride, zirconium silicate, and dry
dolomite.
Water is not generally accepted as an effective
extinguishing agent for metal fires. When applied to hot
burning metal, water will break down into its basic atoms of
oxygen and hydrogen. This chemical breakdown contributes to
the combustion of the metal. However, water is also a good
universal coolant and can be used on some combustible metals,
but only under proper conditions and application, to reduce
the temperature of the burning metal below the ignition point.
For example, automatic deluge systems in magnesium plants can
discharge such large quantities of water on burning magnesium
that the fire will be extinguished. The National Fire
Protection Association has specific standards for this type of
automatic sprinkler system. Further information on the
control of metal fires with water can be found in the National
Fire Protection Association's Fire Protection Handbook.
An excellent source of selection and distribution
criteria is found in the National Fire Protection
Association's Standard No. 10. Other sources of information
include the National Safety Council and the employer's fire
insurance carrier.
(5) Substitution of standpipe systems for portable fire
extinguishers. The employer is permitted to substitute
acceptable standpipe systems for portable fire extinguishers
under certain circumstances. It is necessary to assure that
any substitution will provide the same coverage that portable
units provide. This means that fire hoses, because of their
limited portability, must be spaced throughout the protected
area so that they can reach around obstructions such as
columns, machinery, etc., and so that they can reach into
closets and other enclosed areas.
(6) Inspection, maintenance and testing. The ultimate
responsibility for the inspection, maintenance and testing of
portable fire extinguishers lies with the employer. The
actual inspection, maintenance, and testing may, however, be
conducted by outside contractors with whom the employer has
arranged to do the work. When contracting for such work, the
employer should assure that the contractor is capable of
performing the work that is needed to comply with this
standard.
If the employer should elect to perform the inspection,
maintenance, and testing requirements of this section
in-house, then the employer must make sure that those persons
doing the work have been trained to do the work and to
recognize problem areas which could cause an extinguisher to
be inoperable. The National Fire Protection Association
provides excellent guidelines in its standard for portable
fire extinguishers. The employer may also check with the
manufacturer of the unit that has been purchased and obtain
guidelines on inspection, maintenance, and testing. Hydrostatic testing is a process that should be left to
contractors or individuals using suitable facilities and
having the training necessary to perform the work.
Any time the employer has removed an extinguisher from
service to be checked or repaired, alternate equivalent
protection must be provided. Alternate equivalent protection
could include replacing the extinguisher with one or more
units having equivalent or equal ratings, posting a fire
watch, restricting the unprotected area from employee
exposure, or providing a hose system ready to operate.
(7) Hydrostatic testing. As stated before, the employer
may contract for hydrostatic testing. However, if the
employer wishes to provide the testing service, certain
equipment and facilities must be available. Employees should
be made aware of the hazards associated with hydrostatic
testing and the importance of using proper guards and water
pressures. Severe injury can result if extinguisher shells
fail violently under hydrostatic pressure.
Employers are encouraged to use contractors who can
perform adequate and reliable service. Firms which have been
certified by the Materials Transportation Board (MTB) of the
United States Department of Transportation (DOT), or state
licensed extinguisher servicing firms, or recognized by the
National Association of Fire Equipment Distributors in
Chicago, Illinois, are generally acceptable for performing
this service.
(8) Training and education. This part of the standard is
of the utmost importance to employers and employees if the
risk of injury or death due to extinguisher use is to be
reduced. If an employer is going to permit an employee to
fight a workplace fire of any size, the employer must make
sure that the employee knows everything necessary to assure
the employee's safety.
Training and education can be obtained through many
channels. Often, local fire departments in larger cities have
fire prevention bureaus or similar organizations which can
provide basic fire prevention training programs. Fire
insurance companies will have data and information available. The National Fire Protection Association and the National
Safety Council will provide, at a small cost, publications
that can be used in a fire prevention program.
Actual firefighting training can be obtained from various
sources in the country. The Texas A and M University, the
University of Maryland's Fire and Rescue Institute, West
Virginia University's Fire Service Extension, Iowa State
University's Fire Service Extension and other state training
schools and land grant colleges have firefighting programs
directed to industrial applications. Some manufacturers of
extinguishers, such as the Ansul Company and Safety First,
conduct fire schools for customers in the proper use of
extinguishers. Several large corporations have taken time to
develop their own on-site training programs which expose
employees to the actual "feeling" of firefighting. Simulated
fires for training of employees in the proper use of
extinguishers are also an acceptable part of a training
program.
In meeting the requirements of this section, the employer
may also provide educational materials, without classroom
instruction, through the use of employee notice campaigns
using instruction sheets or flyers or similar types of
informal programs. The employer must make sure that employees
are trained and educated to recognize not only what type of
fire is being fought and how to fight it, but also when it is
time to get away from it and leave fire suppression to more
experienced firefighters.
[Statutory Authority: RCW 49.17.010, [49.17].040, and[49.17].050
. 01-11-038, § 296-24-59215, filed 5/9/01,
effective 9/1/01. Statutory Authority: Chapter 49.17 RCW. 94-15-096 (Order 94-07), § 296-24-59215, filed 7/20/94,
effective 9/20/94. Statutory Authority: RCW 49.17.040 and 49.17.050. 82-02-003 (Order 81-32), § 296-24-59215, filed
12/24/81.]