WAC 296-24-33017
Processing plants. (1) Scope. This
section shall apply to those plants or buildings which contain
chemical operations such as oxidation, reduction, halogenation,
hydrogenation, alkylation, polymerization, and other chemical
processes but shall not apply to chemical plants, refineries or
distilleries.
(2) Location.
(a) Classification. The location of each processing vessel
shall be based upon its flammable or combustible liquid capacity.
Processing vessels shall be located, with respect to distances
to lines of adjoining property which may be built upon, in
accordance with Table H-20, except when the processing plant is
designed in accordance with (2)(b) of this section.
TABLE H - 20
Processing vessels with
emergency relief venting
to permit pressure
Stable liquids
Unstable liquids
Not in excess of
2.5 p.s.i.g.
Table H-9
2 1/2 times
Table H-9.
Over 2.5. p.s.i.g.
1 1/2 times
Table H-9.
4 times
Table H-9.
(b) Exception. The distances required in (2)(a) of this
section may be waived when the vessels are housed within a
building and the exterior wall facing the line of adjoining
property which may be built upon is a blank wall having a
fire-resistance rating of not less than 4 hours. When Class IA
or unstable liquids are handled, the blank wall shall have
explosion resistance in accordance with good engineering
practice, see (3)(d) of this section.
(3) Processing building.
(a) Construction.
(i) Processing buildings shall be of fire-resistance or
noncombustible construction, except heavy timber construction
with load-bearing walls may be permitted for plants utilizing
only stable Class II or Class III liquids. Except as provided in
(2)(b) of this section or in the case of explosion resistant
walls used in conjunction with explosion relieving facilities,
see (3)(d) of this section, loadbearing walls are prohibited. Buildings shall be without basements or covered pits.
(ii) Areas shall have adequate exit facilities arranged to
prevent occupants from being trapped in the event of fire. Exits
shall not be exposed by the drainage facilities described in
(3)(b) of this section.
(b) Drainage.
(i) Emergency drainage systems shall be provided to direct
flammable or combustible liquid leakage and fire protection water
to a safe location. This may require curbs, scuppers, or special
drainage systems to control the spread of fire, see WAC 296-24-33005 (2)(g)(ii).
(ii) Emergency drainage systems, if connected to public
sewers or discharged into public waterways, shall be equipped
with traps or separators.
(iii) The processing plant shall be designed and operated to
prevent the normal discharge of flammable or combustible liquids
to public waterways, public sewers, or adjoining property.
(c) Ventilation.
(i) Enclosed processing buildings shall be ventilated at a
rate of not less than 1 cubic foot per minute per square foot of
solid floor area. This shall be accomplished by natural or
mechanical ventilation with discharge or exhaust to a safe
location outside of the building. Provision shall be made for
introduction of makeup air in such a manner as not to short
circuit the ventilation. Ventilation shall be arranged to
include all floor areas or pits where flammable vapors may
collect.
(ii) Equipment used in a building and the ventilation of the
building shall be designed so as to limit flammable vapor-air
mixtures under normal operating conditions to the interior of
equipment, and to not more than 5 feet from equipment which
exposes Class I liquids to the air. Examples of such equipment
are dispensing stations, open centrifuges, plate and frame
filters, open vacuum filters, and surfaces of open equipment.
(d) Explosion relief. Areas where Class IA or unstable
liquids are processed shall have explosion venting through one or
more of the following methods:
(i) Open air construction.
(ii) Lightweight walls and roof.
(iii) Lightweight wall panels and roof hatches.
(iv) Windows of explosion venting type.
(4) Liquid handling.
(a) Storage.
(i) The storage of flammable or combustible liquids in tanks
shall be in accordance with the applicable provisions of WAC 296-24-33005.
(ii) If the storage of flammable or combustible liquids in
outside aboveground or underground tanks is not practical because
of temperature or production considerations, tanks may be
permitted inside of buildings or structures in accordance with
the applicable provisions of WAC 296-24-33005.
(iii) Storage tanks inside of buildings shall be permitted
only in areas at or above grade which have adequate drainage and
are separated from the processing area by construction having a
fire resistance rating of at least 2 hours.
(iv) The storage of flammable or combustible liquids in
containers shall be in accordance with the applicable provisions
of WAC 296-24-33009.
(b) Piping, valves, and fittings.
(i) Piping, valves, and fittings shall be in accordance with
WAC 296-24-33007.
(ii) Approved flexible connectors may be used where
vibration exists or where frequent movement is necessary. Approved hose may be used at transfer stations.
(iii) Piping containing flammable or combustible liquids
shall be identified.
(c) Transfer.
(i) The transfer of large quantities of flammable or
combustible liquids shall be through piping by means of pumps or
water displacement. Except as required in process equipment,
gravity flow shall not be used. The use of compressed air as a
transferring medium is prohibited.
(ii) Positive displacement pumps shall be provided with
pressure relief discharging back to the tank or to pump suction.
(d) Equipment.
(i) Equipment shall be designed and arranged to prevent the
unintentional escape of liquids and vapors and to minimize the
quantity escaping in the event of accidental release.
(ii) Where the vapor space of equipment is usually within
the flammable range, the probability of explosion damage to the
equipment can be limited by inerting, by providing an explosion
suppression system, or by designing the equipment to contain the
peak explosion pressure which may be modified by explosion
relief. Where the special hazards of operation, sources of
ignition, or exposures indicate a need, consideration shall be
given to providing protection by one or more of the above means.
(5) Tank vehicle and tank car loading and unloading. Tank
vehicle and tank car loading or unloading facilities shall be
separated from aboveground tanks, warehouses, other plant
buildings, or nearest line of adjoining property which may be
built upon by a distance of 25 feet for Class I liquids and 15
feet for Class II and Class III liquids measured from the nearest
position of any fill stem. Buildings for pumps or shelters for
personnel may be a part of the facility. Operations of the
facility shall comply with the appropriate portions of WAC 296-24-33013(3).
(6) Fire control.
(a) Portable extinguishers. Approved portable fire
extinguishers of appropriate size, type and number shall be
provided.
(b) Other controls. Where the special hazards of operation
or exposure indicate a need, the following fire control provision
shall be provided.
(i) A reliable water supply shall be available in pressure
and quantity adequate to meet the probable fire demands.
(ii) Hydrants shall be provided in accordance with accepted
good practice.
(iii) Hose connected to a source of water shall be installed
so that all vessels, pumps, and other equipment containing
flammable or combustible liquids can be reached with at least one
hose stream. Nozzles that are capable of discharging a water
spray shall be provided.
(iv) Processing plants shall be protected by an approved
automatic sprinkler system or equivalent extinguishing system. If special extinguishing systems including but not limited to
those employing foam, carbon dioxide, or dry chemical are
provided, approved equipment shall be used and installed in an
approved manner.
(c) Alarm systems. An approved means for prompt
notification of fire to those within the plant and any public
fire department available shall be provided. It may be advisable
to connect the plant system with the public system where public
fire alarm system is available.
(d) Maintenance. All plant fire protection facilities shall
be adequately maintained and periodically inspected and tested to
make sure they are always in satisfactory operating condition and
that they will serve their purpose in time of emergency.
(7) Sources of ignition.
(a) General.
(i) Precautions shall be taken to prevent the ignition of
flammable vapors. Sources of ignition include but are not
limited to open flames; lightning; smoking; cutting and welding;
hot surfaces; frictional heat; static, electrical, any mechanical
sparks; spontaneous ignition, including heat-producing chemical
reactions; and radiant heat.
(ii) Class I liquids shall not be dispensed into containers
unless the nozzle and container are electrically interconnected. Where the metallic floorplate on which the container stands while
filling is electrically connected to the fill stem or where the
fill stem is bonded to the container during filling operations by
means of a bond wire, the provisions of this section shall be
deemed to have been complied with.
(b) Maintenance and repair.
(i) When necessary to do maintenance work in a flammable or
combustible liquid processing area, the work shall be authorized
by a responsible representative of the employer.
(ii) Hot work such as welding or cutting operations, use of
spark-producing power tools, and chipping operations shall be
permitted only under supervision of an individual in responsible
charge who shall make an inspection of the area to be sure that
it is safe for the work to be done and that safe procedures will
be followed for the work specified.
(c) Electrical.
(i) All electrical wiring and equipment within storage or
processing areas shall be installed according to chapter 296-24
WAC Part L.
(ii) Locations where flammable vapor-air mixtures may exist
under normal operations shall be classified Class I, Division 1
according to the requirements of chapter 296-24 WAC Part L. For
those pieces of equipment installed in accordance with (3)(c)(ii)
of this section, the Division 1 area shall extend 5 feet in all
directions from all points of vapor liberation. All areas within
pits shall be classified Division 1 if any part of the pit is
within a Division 1 or 2 classified area, unless the pit is
provided with mechanical ventilation.
(iii) Locations where flammable vapor-air mixtures may exist
under abnormal conditions and for a distance beyond Division 1
locations shall be classified Division 2 according to the
requirements of chapter 296-24 WAC Part L. These locations
include an area within 20 feet horizontally, 3 feet vertically
beyond a Division 1 area, and up to 3 feet above floor or grade
level within 25 feet, if indoors, or 10 feet if outdoors, from
any pump, bleeder, withdrawal fittings, meter, or similar device
handling Class I liquids. Pits provided with adequate mechanical
ventilation within a Division 1 or 2 area shall be classified
Division 2. If Class II or Class III liquids only are handled,
then ordinary electrical equipment is satisfactory though care
shall be used in locating electrical apparatus to prevent hot
metal from falling into open equipment.
(iv) Where the provisions of (7)(c)(i), (ii), and (iii) of
this section require the installation of explosion-proof
equipment, ordinary electrical equipment including switchgear may
be used if installed in a room or enclosure which is maintained
under positive pressure with respect to the hazardous area. Ventilation makeup air shall be uncontaminated by flammable
vapors.
(8) Housekeeping.
(a) General. Maintenance and operating practices shall be
in accordance with established procedures which will tend to
control leakage and prevent the accidental escape of flammable or
combustible liquids. Spills shall be cleaned up promptly.
(b) Access. Adequate aisles shall be maintained for
unobstructed movement of personnel and so that fire protection
equipment can be brought to bear on any part of the processing
equipment.
(c) Waste and residues. Combustible waste material and
residues in a building or operating area shall be kept to a
minimum, stored in closed metal waste cans, and disposed of
daily.
(d) Clear zone. Ground area around buildings and operating
areas shall be kept free of tall grass, weeds, trash, or other
combustible materials.
[Statutory Authority: Chapter 49.17 RCW. 91-24-017 (Order
91-07), § 296-24-33017, filed 11/22/91, effective 12/24/91. Statutory Authority: RCW 49.17.040 and 49.17.050. 85-10-004
(Order 85-09), § 296-24-33017, filed 4/19/85; Order 76-6, §
296-24-33017, filed 3/1/76; Order 73-5, § 296-24-33017, filed
5/9/73 and Order 73-4, § 296-24-33017, filed 5/7/73.]