Type of tank |
Protection |
Minimum distance in feet from property line which may be built upon, including the opposite side of a public way. | Minimum distance in feet from nearest side of any public way or from nearest important building and shall be not less than 5 feet. | ||||
| Floating roof ——— |
Protection for exposures. | 1/2 times diameter of tank but need not exceed 90 ft. | 1/6 times diameter
of tank but need
not exceed 30 ft. |
||||
| None ———–– | Diameter of tank but need not exceed 175 ft. | 1/6 times diameter of tank but need not exceed 30 ft. | |||||
| Vertical
with weak
roof to
shell seam |
Approved foam or inerting system on the tank. | 1/2 times diameter of tank but need not exceed 90 ft. and shall not be less than 5 ft. | 1/6 times diameter of tank but need not exceed 30 ft. | ||||
| Protection for exposures. | Diameter of tank but need not exceed 175 ft. | 1/3 times diameter of tank but need not exceed 60 ft. | |||||
| None ———–– | 2 times diameter of tank but need not exceed 350 ft. | 1/3 times diameter
of tank but need
not exceed 60 ft. |
|||||
| Horizontal and vertical, with emergency relief venting to limit pressures to 2.5 p.s.i.g. | Approved inerting system on the tank or approved foam system on vertical tanks. | 1/2 times Table H-9 but shall not be less than 5 ft. | 1/2 times Table H-9. | ||||
| Protection for exposures. | Table H-9 ———– | Table H-9 | |||||
| None ———– | 2 times table —— | Table H-9 | |||||
Type of tank |
Protection |
Minimum distance in feet from property line which may be built upon, including the opposite side of a public way. | Minimum
distance in feet from nearest side of any public way or from nearest important building. |
||||
| Any type | - | Protection for exposures. | 1 1/2 times Table H-9 but shall not be less than 25 ft. | 1 1/2 times Table H-9 but shall not be less than 25 ft. | |||
| None ————– | 3 times Table H-9 but shall not be less than 50 ft. | 1 1/2 times Table H-9 but shall not be less than 25 ft. | |||||
Type of tank |
Protection |
Minimum distance in feet from property line which may be built upon, including the opposite side of a public way. | Minimum distance in feet from nearest side of any public way or from nearest important building. | ||||
| Floating roof ——— |
Protection for exposures. | Diameter of tank but need not exceed 175 ft. | 1/3 times
diameter of tank
but need not
exceed 60 ft. |
||||
| None ———— | 2 times diameter of tank but need not exceed 350 ft. | 1/3 times
diameter of tank
but need not
exceed 60 ft. |
|||||
| Fixed roof ——— |
Approved foam or inerting system. | Diameter of tank but need not exceed 175 ft. | 1/3 times
diameter of tank
but need not
exceed 60 ft. |
||||
| Protection for exposures. |
2 times diameter of tank but need not exceed 350 ft. | 2/3 times
diameter of tank
but need not
exceed 120 ft. |
|||||
| None ———— | 4 times diameter of tank but need not exceed 350 ft. | 2/3 times diameter of tank but need not exceed 120 ft. | |||||
Type of tank |
Protection |
Minimum distance in feet from property line which may be built upon, including the opposite side of a public way. | Minimum distance in feet from nearest side of any public way or from nearest important building. | ||||
| Horizontal and vertical tanks with emergency relief venting to permit pressure not in excess of 2.5 p.s.i.g. | Tank
protected
with any of
the following: Approved water spray, approved inerting, approved insulation and refrigeration, approved barricade. |
See Table H-9, but the distance may be not less than 25 ft. | Not less than 25 ft. | ||||
| Protection for exposures. | 2 1/2 times Table H-9 but not less than 50 ft. | Not less than 50 ft. | |||||
| None ——— | 5 times Table H-9 but not less than 100 ft. | Not less than 100 ft. | |||||
| Horizontal and vertical tanks with emergency relief venting to permit pressure over 2.5 p.s.i.g. | Tank
protected
with any one
of the
following: Approved water spray, approved inerting, approved insulation and refrigeration, approved barricade. |
2 times Table H-9 but not less than 50 ft. | Not less than 50 ft. | ||||
| Protection for exposures. | 4 times Table
H-9 but not less
than 100 ft. |
Not less than 100 ft. | |||||
| None ———— | 8 times Table H-9 but not less than 150 ft. | Not less than 150 ft. | |||||
Capacity tank gallons |
Minimum distance in feet from property line which may be built upon, including the opposite side of a public way. |
Minimum distance in feet from nearest side of any public way or from nearest important building. |
|||||||||
| 275 | or less | —–—–———— 5 | 5 | ||||||||
| 276 | to | 750 | –——— 10 | 5 | |||||||
| 751 | to | 12,000 | –——— 15 | 5 | |||||||
| 12,001 | to | 30,000 | –——— 20 | 5 | |||||||
| 30,001 | to | 50,000 | –——— 30 | 10 | |||||||
| 50,001 | to | 100,000 | –——— 50 | 15 | |||||||
| 100,001 | to | 500,000 | –——— 80 | 25 | |||||||
| 500,001 | to | 1,000,000 | —–—- 100 | 35 | |||||||
| 1,000,001 | to | 2,000,000 | –——- 135 | 45 | |||||||
| 2,000,001 | to | 3,000,000 | –——- 165 | 55 | |||||||
| 3,000,001 | or more | —––———— 175 | 60 | ||||||||
| Exemption: | Tanks of 3,000 bbls. capacity or less containing crude petroleum in crude-producing areas; and, outside aboveground atmospheric tanks under 1,000 gallons capacity containing other than Class IA flammable liquids may have open vents. (See (2)(f)(ii) of this section.) |
| Square feet |
CFH | Square feet |
CFH | Square feet |
CFH | |||||
| 20 | 21,100 | 200 | 211,000 | 1,000 | 524,000 | |||||
| 30 | 31,600 | 250 | 239,000 | 1,200 | 557,000 | |||||
| 40 | 42,100 | 300 | 265,000 | 1,400 | 587,000 | |||||
| 50 | 52,700 | 350 | 288,000 | 1,600 | 614,000 | |||||
| 60 | 63,200 | 400 | 312,000 | 1,800 | 639,000 | |||||
| 70 | 73,700 | 500 | 354,000 | 2,000 | 662,000 | |||||
| 80 | 84,200 | 600 | 392,000 | 2,400 | 704,000 | |||||
| 90 | 94,800 | 700 | 428,000 | 2,800 | 742,000 | |||||
| 100 | 105,000 | 800 | 462,000 | and | ||||||
| 120 | 126,000 | 900 | 493,000 | over | ||||||
| 140 | 147,000 | 1,000 | 524,000 | |||||||
| 160 | 168,000 | |||||||||
| 180 | 190,000 | |||||||||
| 200 | 211,000 | |||||||||
| CFH = 1,107A0.82 | |
| Where: | |
| CFH = | Venting requirement, in cubic feet of free air per hour. |
| A = | Exposed wetted surface, in square feet. |
| Note: | The foregoing formula is based on Q = 21,000A0.82. |
| Cubic feet of free air per hour = V | ||||
| V = | 1337 L M |
|||
| V = | Cubic feet of free air per hour from Table H-10. | |||
| L = | Latent heat of vaporization of specific liquid in B.t.u. per pound. | |||
| M = | Molecular weight of specific liquids. | |||
| 0.5 for drainage in accordance with (2)(g)(ii) of this section for tanks over 200 square feet of wetted area. |
| 0.3 for approved water spray. |
| 0.3 for approved insulation. |
| 0.15 for approved water spray with approved insulation. |
Maximum flow GPM |
Pipe length* |
||||
50 feet |
100 feet |
200 feet |
|||
Inches |
Inches |
Inches |
|||
| 100 | ————— | 1 1/4 | 1 1/4 | 1 1/4 | |
| 200 | ————— | 1 1/4 | 1 1/4 | 1 1/4 | |
| 300 | ————— | 1 1/4 | 1 1/4 | 1 1/2 | |
| 400 | ————— | 1 1/4 | 1 1/2 | 2 | |
| 500 | ————— | 1 1/2 | 1 1/2 | 2 | |
| 600 | ————— | 1 1/2 | 2 | 2 | |
| 700 | ————— | 2 | 2 | 2 | |
| 800 | ————— | 2 | 2 | 3 | |
| 900 | ————— | 2 | 2 | 3 | |
| 1,000 | ————— | 2 | 2 | 3 |
|