WAC 246-359-410
Foundations and footings for concrete
masonry units (CMU) walls. (1) Footings for load bearing CMU
walls must be continuous concrete having a minimum twelve
width-by-ten inch thickness, placed a minimum eighteen inches
below the finished grade, and reinforced with a minimum of two
No. 4 continuous rebar.
(2) Foundations must be one of the following:
(a) Concrete reinforced vertically and horizontally with No.
4 rebar at twenty-four inches on center; or
(b) CMU reinforced vertically and horizontally with No. 4
rebar and having all cells below finished grade fully grouted.
(3) Vertical reinforcement must be spaced at four feet on
center, within twelve inches of each corner, extend at least
twenty inches up into the CMU wall, and extend at least six
inches into the footing with an additional six inches bent at
ninety degrees and tied to the horizontal footing rebar.
(4) Foundations must be six inches in width or the width of
the CMU wall, whichever is greater.
[Statutory Authority: RCW 70.114A.081. 99-03-065, §
246-359-410, filed 1/18/99, effective 2/18/99.]