WAC 246-359-330
Roof framing ventilation for wood framed
construction and concrete masonry units (CMU). (1) Ventilation
must be provided for enclosed roof framing spaces by providing
sixteen-mesh screened openings at:
(a) The eaves;
(b) The gable ends;
(c) The ridge; or
(d) Any combination of (a) through (c) of this subsection.
(2) The minimum amount of ventilation openings must be at
the rate of one square foot of net free opening for every
three-hundred square feet of attic area.
[Statutory Authority: RCW 70.114A.081. 99-03-065, §
246-359-330, filed 1/18/99, effective 2/18/99.]