WAC 246-335-245
Plumbing. An applicant must design and
install plumbing, including:
(1) Backflow prevention with devices on plumbing
fixtures, equipment, facilities, buildings, premises, or areas
which may cause actual or potential cross-connections of
systems in order to prevent the backflow of water or other
liquids, gases, mixtures, or substances into a water
distribution system or other fixtures, equipment, facilities,
buildings, or areas;
(2) Trap primers in floor drains and stand pipes subject
to infrequent use;
(3) Wrist, knee or foot faucet controls or equivalent and
gooseneck spouts without aerators on handwash sinks;
(4) Insulation on:
(a) Hot water piping systems;
(b) Cold water and drainage piping; and
(c) Piping exposed to outside temperatures; and
(5) Equipment to deliver hot water at point of use as
follows:
(a) 120°F or less for handwash sinks and bathing
fixtures;
(b) 160°F or more for laundry washers;
(c) 120°F or more for laundry washers using chemical
sanitization;
(d) 120°F or more for mechanical dishwashers using
chemical sanitization;
(e) 140°F or more for mechanical dishwashers using high
temperature sanitization; and
(f) 180°F or more for sanitization cycle in high
temperature mechanical dishwashers.