WAC 246-293-650
Minimum standards for fire hydrants. (1)
In those areas where minimum fire flow requirements must be met,
fire hydrants shall be provided in accordance with WAC 248-57-600. If phased installation of water facilities are
approved by the department, fire hydrants do not need to be
installed until source, storage, and transmission capacity needed
to meet the minimum flow requirements are operational: Provided,
That in such instances a "T" shall be installed every 900 feet
where fire hydrants will be located.
(2) Fire hydrants shall be located at roadway intersections
wherever possible and the distance between them shall be no
further than 900 feet.
(3) All fire hydrants shall conform to American Water Works
Association specifications for dry barrel fire hydrants. Each
hydrant shall have at least two hose connections of 2 1/2"
diameter each and one pumper connection. All connections must
have national standard threads or other connection devices
consistent with local fire protection authority requirements.
(4) Fire hydrants shall be installed plumb and be set to the
finished grade. The bottom of the lowest outlet of the hydrant
shall be no less than eighteen inches above the grade. There
shall be thirty-six inches of clear area about the hydrant for
operation of a hydrant wrench on the outlets and on the control
valve. The pumper port shall face the most likely route of
approach of the fire truck as determined by the local fire
protection authority.
(5) Fire hydrants shall be located so as to be accessible by
fire engines and not be obstructed by any structure or vegetation
or have the visibility impaired for a distance of fifty feet in
the direction of vehicular approach to the hydrant. Fire
hydrants subject to vehicle damage (e.g., such as those located
in parking lots) shall be adequately protected.
(6) Provisions shall be made to drain fire hydrant barrels
to below the depth of maximum frost penetration.
(7) Out of service fire hydrants shall be repaired as soon
as possible.
(8) Public water systems are encouraged to enter into
contracts with local fire protection authorities to insure proper
maintenance of fire hydrants.
[Statutory Authority: RCW 43.70.040. 91-02-049 (Order 121),
recodified as § 246-293-650, filed 12/27/90, effective 1/31/91. Statutory Authority: RCW 70.116.080. 79-04-007 (Order 1378), §
248-57-600, filed 3/12/79.]