WAC 246-290-672
Interim treatment requirements. (1)
Purveyors of existing unfiltered systems installing filtration
shall provide interim disinfection treatment to:
(a) Ensure compliance with the monthly coliform MCL under
WAC 246-290-310;
(b) Achieve inactivation levels of Giardia lamblia cysts
on a daily basis each month the system serves water to the
public as directed by the department; and
(c) Maintain a detectable residual disinfectant
concentration in the distribution system, measured as total
chlorine, free chlorine, or combined chlorine in 95 percent or
more of the samples taken each calendar month. Water in the
distribution system with an HPC level less than or equal to
500 organisms/ml is considered to have a detectable residual
disinfectant concentration for the purposes of compliance with
this subsection.
(2) Failure to provide the required level of inactivation
in subsection (1)(b) of this section on more than one day in
any calendar month shall be considered a treatment technique
violation.
(3) The department may require the purveyor to provide
higher levels of treatment than specified in subsection (1)(b)
of this section when necessary to protect the health of
consumers served by the public water system.
(4) Interim treatment requirements shall be met in
accordance with a schedule acceptable to the department.
[Statutory Authority: RCW 43.20.050 (2) and (3) and70.119A.080
. 03-08-037, § 246-290-672, filed 3/27/03,
effective 4/27/03. Statutory Authority: RCW 43.02.050
[43.20.050]. 99-07-021, § 246-290-672, filed 3/9/99,
effective 4/9/99. Statutory Authority: RCW 43.20.050. 93-08-011 (Order 352B), § 246-290-672, filed 3/25/93,
effective 4/25/93.]