WAC 246-290-451
Disinfection of drinking water. (1) No
portion of a public water system containing potable water
shall be put into service, nor shall service be resumed until
the facility has been effectively disinfected.
(a) In cases of new construction, drinking water shall
not be furnished to the consumer until satisfactory
bacteriological samples have been analyzed by a laboratory
certified by the state; and
(b) In cases of existing water mains, when the integrity
of the main is lost resulting in a significant loss of
pressure that places the main at risk to cross-connection
contamination, the purveyor shall use standard industry
practices such as flushing, disinfection, and/or
bacteriological sampling to ensure adequate and safe water
quality prior to the return of the line to service;
(c) If a cross-connection is confirmed, the purveyor
shall satisfy the reporting requirements as described under
WAC 246-290-490(8).
(2) The procedure used for disinfection shall conform to
standards published by the American Water Works Association,
or other industry standards acceptable to the department.
(3) The purveyor of a system using surface water or GWI
shall meet disinfection requirements specified in Part 6 of
this chapter.
(4) The purveyor of a system using groundwater shall
meet the requirements under subsection (6) of this section if
required by the department to disinfect for any of the
following reasons:
(a) Determination that the groundwater source is in
hydraulic connection to surface water under WAC 246-290-640(4);
(b) A history of unsatisfactory source coliform sampling;
or
(c) A microbiological contaminant threat within the
sanitary control area as defined in WAC 246-290-135.
(5) The purveyor of a groundwater system that is required
to disinfect as a result of becoming a SSNC due to repeated
total coliform MCL or major repeat violations shall meet the
requirements under subsection (7) of this section.
(6) If disinfection is required under subsection (4) of
this section, the following requirements must be met:
(a) Provide a minimum contact time at or before the first
customer of:
(i) Thirty minutes if 0.2 mg/L free chlorine residual is
maintained;
(ii) Ten minutes if 0.6 mg/L free chlorine residual is
maintained; or
(iii) Any combination of free chlorine residual
concentration (C), measured in mg/L and contact time (T),
measured in minutes, that result in a CT product (C x T) of
greater than or equal to six; and
(b) Maintain a detectable residual disinfectant
concentration in all active parts of the distribution system,
measured as total chlorine, free chlorine, combined chlorine,
or chlorine dioxide.
(c) The department may require the purveyor to provide
longer contact times, higher chlorine residuals, or additional
treatment to protect the health of consumers served by the
water system.
(d) To demonstrate the required level of treatment is
maintained, the purveyor shall:
(i) Monitor the residual disinfectant concentration at
the point of entry to the distribution system, or at a
department-approved location, at least once every Monday
through Friday (except holidays) that water is supplied;
(ii) Calculate the daily CT value at or before the first
customer; and
(iii) Submit monthly groundwater treatment reports to the
department using a department-approved form by the tenth day
of the following month.
(e) All analyses required in this subsection shall be
conducted in accordance with EPA standard methods.
(f) The purveyor may be required to monitor the residual
disinfectant concentration each calendar day water is supplied
to the distribution system if the department considers
treatment operation is unreliable.
(g) The department may require the use of continuous
residual analyzers and recorders to assure adequate monitoring
of residual concentrations.
(7) If disinfection is required under subsection (5) of
this section, or a chemical disinfectant is added to a
groundwater source for any other reason, the following
requirements must be met:
(a) Monitor residual disinfectant concentration at
representative points throughout the distribution system once
each day, excluding weekends and holidays, and at the same
time and location of routine and repeat coliform sample
collection. Frequency of disinfection residual monitoring may
be reduced upon written request to the department if it can be
shown that disinfection residuals can be maintained on a
reliable basis without the provision of daily monitoring.
(b) Maintain a detectable residual disinfectant
concentration in all active parts of the distribution system,
measured as total chlorine, free chlorine, combined chlorine,
or chlorine dioxide. Water in the distribution system with an
HPC level less than or equal to 500 organisms/mL is considered
to have a detectable residual disinfectant concentration.
(c) The department may require the purveyor to provide
higher chlorine residuals, or additional treatment to protect
the health of consumers served by the water system.
(d) All analyses required in this subsection shall be
conducted in accordance with EPA standard methods.
(e) The department may require the use of continuous
residual analyzers and recorders to assure adequate monitoring
of residual concentrations.
[Statutory Authority: RCW 43.20.050 and 70.119A.080. 10-20-068, § 246-290-451, filed 9/29/10, effective 11/1/10. Statutory Authority: RCW 43.20.050 (2) and (3) and70.119A.080
. 03-08-037, § 246-290-451, filed 3/27/03,
effective 4/27/03. Statutory Authority: RCW 43.02.050
[43.20.050]. 99-07-021, § 246-290-451, filed 3/9/99,
effective 4/9/99.]