WAC 246-225A-050
Dental X-ray facility design. (1) Each
X-ray exposure button must be located to meet the following
criteria:
(a) For stationary X-ray systems, the X-ray exposure
button must be permanently mounted in a protected area so that
the operator can make an exposure only from the protected
area; and
(b) Mobile X-ray systems must have an X-ray exposure
button located at the end of a cord at least twelve feet (3.7
meters) long.
(2) Shielding for cephalometric X ray must meet the
following criteria:
(a) Be at least one foot (30.5 centimeters) larger, in
both the horizontal and vertical directions, than the area of
the primary beam where it strikes the nearest wall; and
(b) Shielding between the nearest wall struck by the
primary beam and the next occupied area must have two-pound
lead or equivalent installed in the wall. Exterior walls or
concrete block walls need no additional shielding.
(3) Acceptable shielding materials for dental X-ray
facilities are as follows:
(a) The minimum shielding for intra-oral stray radiation
protection is standard gypsum wallboard/sheetrock construction
(two layers each of five-eighths inch thickness).
(b) Where windows are provided to observe patients during
radiography, the windows are at least one-half inch plate
glass, or equivalent ability to reduce exposure.
(c) All other materials used for shielding between
operatories and for operator protection areas are equivalent
to 0.2 millimeters of lead.
(4) Barriers surrounding dental X-ray rooms and dental
operatories where intra-oral X-ray equipment is installed must
meet the following criteria:
(a) Be at least six feet (1.83 meters) high and composed
of materials capable of reducing scattered radiation as
required under subsection (3) of this section;
(b) There must be no line of sight between workers or
patients in one operatory and the X-ray tube housing assembly
in the next operatory when that X-ray tube housing assembly is
in its operating position;
(c) X-ray tube housing assemblies must not be mounted
between operatories on top of barriers less than six feet
(1.83 meters) high, unless those barriers are at the foot end
of the patient chairs, and there is no line of sight between
adjacent operatories.
[Statutory Authority: RCW 70.98.050 and 70.98.080. 11-19-013, § 246-225A-050, filed 9/7/11, effective 10/8/11;
08-14-074, § 246-225A-050, filed 6/26/08, effective 7/27/08.]