| Note: | The establishment of leak indication thresholds is a means of setting a standard for the equipment or method used. It is not in any way meant to imply that actual leak rates less than these limits are allowable. No release is acceptable, and any indication that a release may have occurred should be investigated in accordance with WAC 173-360-360. Manufacturers and certified UST supervisors installing or utilizing leak detection equipment and/or methods must follow EPA's standard test procedures for evaluating leak detection methods to demonstrate compliance with the requirements of subsection (1) of this section. |
| Note: | Practices described in the American Petroleum Institute Publication 1621, "Recommended Practice for Bulk Liquid Stock Control at Retail Outlets," may be used, where applicable, as guidance in meeting the requirements of this paragraph. |
| Nominal Tank Capacity |
Weekly Standard (one test) |
Monthly Standard |
| 550 gallons or less | 10 gallons | 5 gallons |
| 551-1,000 gallons | 13 gallons | 7 gallons |
| 1,001-2,000 gallons | 26 gallons | 13 gallons |
| 2,001 gallons or more* | .75% of capacity | .5% of capacity |
| (*Emergency Power Generator Tanks only.) | ||
| Nominal Tank Capacity | Monthly Standard |
| 550 gallons or less | 5 gallons |
| 551-1,000 gallons | 7 gallons |
| 1,001-2000 gallons | 13 gallons |
| Note: | Monitoring wells must also comply with the minimum standards for construction, maintenance, and abandonment of resource protection wells specified in chapter 173-160 WAC. UST system owners and operators are encouraged to retain the services of a qualified professional who is experienced in determining the design and placement of vapor monitoring wells surrounding an UST system. |
| Note: | Monitoring wells must also comply with the minimum standards for construction, maintenance, and abandonment of wells specified in chapter 173-160 WAC. UST system owners and operators are encouraged to retain the services of a qualified professional who is experienced in determining the design and placement of groundwater monitoring wells surrounding an UST system. |
| Note: | The provisions outlined in the Steel Tank Institute's "Standard for Dual Wall Underground Storage Tanks" may be used as guidance for aspects of the design and construction of underground steel double-walled tanks. |