WAC 173-180-330
Storage tank requirements. (1) Storage
tanks constructed after the adoption date of this section must
meet or exceed the 1993 version of the National Fire
Protection Association (NFPA No. 30) requirements and one of
the following design and manufacturing standards:
(a) UL No. 142, Steel Aboveground Tanks for Flammable and
Combustible Liquids dated April 1993;
(b) API Standard 650, Welded Steel Tanks for Oil Storage
dated November 1988;
(c) API Standard 620, Design and Construction of Large
Welded, Low-Pressure Tanks dated June 1990; or
(d) Another standard approved by ecology.
(2) The owner or operator must ensure that the means of
preventing storage tank overfill comply with the 1993 version
of the National Fire Protection Association (NFPA), Flammable
and Combustible Code, No. 30, Chapter 2, Section 2-10.
(3) Storage tanks must be maintained, repaired and
inspected in accordance with the requirements of API 653 dated
January 1991, unless the operator proposes an equivalent
inspection strategy which is approved by ecology.
(4) A record of all inspection results and corrective
actions taken must be kept for the service life of the tank
and must be available to ecology for inspection and copying
upon request.
[Statutory Authority: RCW 88.46.160, 88.46.165, and chapter 90.56 RCW. 06-20-034 (Order 06-02), § 173-180-330, filed
9/25/06, effective 10/26/06.]