WAC 51-56-0900
Chapter 9 -- Vents.
903.1.2 ABS and PVC DWV piping installations shall be
installed in accordance with applicable standards in Table
14-1. Except for individual single family dwelling units,
materials exposed within ducts or plenums shall have a
flame-spread index of not more than 25 and a smoke developed
index of not more than 50, when tested in accordance with the
Test for Surface-Burning Characteristics of the Building
Materials (see the Building Code standards based on ASTM E-84
and ANSI/UL 723).
908.2.1 Where Permitted. Water closets, bathtubs, showers,
bidets, and floor drains within one or two bathroom groups
located on the same floor level and for private use shall be
permitted to be vented by a wet vent. The wet vent shall be
considered the vent for the fixtures and shall extend from the
connection of the dry vent along the direction of the flow in
the drain pipe to the most downstream fixture drain or trap
arm connection to the horizontal branch drain. Each
wet-vented fixture drain or trap arm shall connect
independently to the wet-vented horizontal branch drain. Each
individual fixture drain or trap arm shall connect
horizontally to the wet-vented horizontal branch drain or
shall be provided with a dry vent. The trap to vent distance
shall be in accordance with Table 10-1. Only the fixtures
within the bathroom groups shall connect to the wet-vented
horizontal branch drain. The water closet fixture drain or
trap arm connection to the wet vent shall be downstream of any
fixture drain or trap arm connections. Any additional
fixtures shall discharge downstream of the wet-vent system and
be conventionally vented.
[Statutory Authority: RCW 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-101, § 51-56-0900, filed 1/20/10,
effective 7/1/10. Statutory Authority: RCW 19.27.190,
19.27.020 and chapters 19.27 and 34.05 RCW. 07-01-094, §
51-56-0900, filed 12/19/06, effective 7/1/07. Statutory
Authority: RCW 19.27.031, 19.27.074. 02-01-114, §
51-56-0900, filed 12/18/01, effective 7/1/02.]