| EXCEPTION: | Provisions of this code that specifically apply to existing conditions are retroactive. See Sections 402.3, 601.1 and Appendix A. |
| EXCEPTIONS: | 1. Structures constructed to meet the requirements for the class of ignition-resistant construction specified in Table 503.1 for a nonconforming water supply. |
| 2. Buildings containing only private garages, carports, sheds and agricultural buildings with a floor area of not more than 600 square feet (56 m2). |
| Fire Hazard Severity | ||||||
| Moderate Hazard | High Hazard | Extreme Hazard | ||||
| Water Supplyb | Water Supplyb | Water Supplyb | ||||
| Defensible Spacec | Conforming | Nonconforming | Conforming | Nonconforming | Conforming | Nonconforming |
| Nonconforming | IR 2 | IR 1 | IR 1 | IR 1 N.C. | IR 1 N.C. | Not Permitted |
| Conforming | IR 3 | IR 2 | IR 2 | IR 1 | IR 1 | IR 1 N.C. |
| 1.5 x Conforming | Not Required | IR 3 | IR 3 | IR 2 | IR 2 | IR 1 |
| a. Access shall be in accordance with Section 402. | |
| b. Water supply shall be in accordance with Section 402.1. | |
| IR 1 = Ignition-resistant construction in accordance with Section 504. | |
| IR 2 = Ignition-resistant construction in accordance with Section 505. | |
| IR 3 = Ignition-resistant construction in accordance with Section 506. | |
| N.C. = Exterior walls shall have a fire-resistance rating of not less than 1 hour and the exterior surfaces of such walls shall be noncombustible. Usage of log wall construction is allowed. | |
| c. Conformance based on Section 603. |