| EXCEPTION: | Group U occupancies. |
| EXCEPTIONS: | 1. Vertical opening protection is not required for Group R-3 occupancies. |
| 2. Vertical opening protection is not required for open parking garages and ramps. | |
| 3. Vertical opening protection is not required for escalators. |
| EXCEPTIONS: | 1. Vertical opening protection is not required for Group R-3 occupancies. |
| 2. Vertical opening protection is not required for open parking garages and ramps. | |
| 3. Vertical opening protection is not required for escalators. |
![]() |
| EXCEPTIONS: | 1. Vertical opening protection is not required for Group R-3 occupancies. |
| 2. Vertical opening protection is not required for open parking garages and ramps. |
| EXCEPTION: | Occupancies with an existing, previously approved fire alarm system. |
| EXCEPTIONS: | 1. A manual fire alarm system is not required in a building with a maximum area of 1,000 square feet (93 m2) that contains a single classroom and is located no closer than 50 feet (15,240 mm) from another building. |
| 2. A manual fire alarm system is not required in Group E occupancies with an occupant load less than 50. |
| EXCEPTIONS: | 1. Manual fire alarm boxes in resident or patient sleeping areas shall not be required at exits if located at all nurses' control stations or other constantly attended staff locations, provided such stations are visible and continuously accessible and that travel distances required in Section 907.5.2 are not exceeded. |
| 2. Where each sleeping room has a means of egress door opening directly to an exterior egress balcony that leads directly to the exits in accordance with WAC 51-50-1019, and the building is not more than three stories in height. |
| EXCEPTION: | Manual fire alarm boxes in resident or patient sleeping areas shall not be required at exits if located at all nurses' control stations or other constantly attended staff locations, provided such stations are visible and continuously accessible and that travel distances required in Section 907.5.2.1 are not exceeded. |
| EXCEPTIONS: | 1. Buildings less than two stories in height where all sleeping units, attics and crawl spaces are separated by 1-hour fire-resistance-rated construction and each sleeping unit has direct access to a public way, exit court or yard. |
| 2. Manual fire alarm boxes are not required throughout the building when the following conditions are met: | |
| 2.1. The building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2; | |
| 2.2. The notification appliances will activate upon sprinkler water flow; and | |
| 2.3. At least one manual fire alarm box is installed at an approved location. |
| EXCEPTION: | An automatic smoke detection system is not required in buildings that do not have interior corridors serving sleeping units and where each sleeping unit has a means of egress door opening directly to an exit or to an exterior exit access that leads directly to an exit. |
| EXCEPTION: | Buildings less than two stories in height where all sleeping units, attics and crawl spaces are separated by 1-hour fire-resistance-rated construction and each sleeping unit has direct access to a public way, exit court or yard. |
| EXCEPTION: | Buildings equipped with single-station smoke alarms meeting or exceeding the requirements of Section 907.2.10.1 and where the fire alarm system includes at least one manual fire alarm box per floor arranged to initiate the alarm. |
| EXCEPTIONS: | 1. Where each living unit is separated from other contiguous living units by fire barriers having a fire-resistance rating of not less than 0.75 hour, and where each living unit has either its own independent exit or its own independent stairway or ramp discharging at grade. |
| 2. A separate fire alarm system is not required in buildings that are equipped throughout with an approved supervised automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 and having a local alarm to notify all occupants. | |
| 3. A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units and are protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, provided that dwelling units either have a means of egress door opening directly to an exterior exit access that leads directly to the exits or are served by open-ended corridors designed in accordance with Section 1023.6, Exception 4. |
| EXCEPTIONS: | 1. Where there are interconnected smoke alarms meeting the requirements of Section 907.2.11 and there is at least one manual fire alarm box per floor arranged to continuously sound the smoke alarms. |
| 2. Other manually activated, continuously sounding alarms approved by the fire code official. |
| EXCEPTIONS: | 1. Interconnection is not required in buildings that are not undergoing alterations, repairs or construction of any kind. |
| 2. Smoke alarms in existing areas are not required to be interconnected where alterations or repairs do not result in the removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available which could provide access for interconnection without the removal of interior finishes. |
| EXCEPTIONS: | 1. Smoke alarms are permitted to be solely battery operated in existing buildings where no construction is taking place. |
| 2. Smoke alarms are permitted to be solely battery operated in buildings that are not served from a commercial power source. | |
| 3. Smoke alarms are permitted to be solely battery operated in existing areas of buildings undergoing alterations or repairs that do not result in the removal of interior walls or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available which could provide access for building wiring without the removal of interior finishes. |
| EXCEPTION: | Means of egress conforming to the requirements of the building code under which they were constructed and Section 1030 shall not be required to comply with 4604.2 through 4604.21. |
| EXCEPTIONS: | 1. Elevators used as an accessible means of egress where allowed by Section 1007.4. |
| 2. Previously approved escalators and moving walks in existing buildings. |
| EXCEPTION: | Approved self-luminous signs that provide evenly illuminated letters shall have a minimum luminance of 0.06 foot-lamberts (0.21 cd/m2). |
| EXCEPTION: | Approved signs that provide continuous illumination independent of external power sources are not required to be connected to an emergency electrical system. |
| EXCEPTION: | Assembly occupancies used exclusively as a place of worship and having an occupant load of less than 300. |
| EXCEPTION: | Buildings used only during daylight hours which are provided with windows for natural light in accordance with the International Building Code. |
| EXCEPTION: | Buildings less than 3,000 square feet (279 m2) in gross sales area on one story only, excluding mezzanines. |
| EXCEPTION: | Where each sleeping unit has direct access to the outside of the building at grade. |
| EXCEPTION: | Where each dwelling unit or sleeping unit has direct access to the outside of the building at grade. |
| EXCEPTION: | Where each sleeping unit has direct access to the outside of the building at ground level. |
| EXCEPTIONS: | 1. Existing guards on the open side of stairs shall be not less than 30 inches (760 mm) high. |
| 2. Existing guards within dwelling units shall be not less than 36 inches (910 mm) high. | |
| 3. Existing guards in assembly seating areas. |
| EXCEPTIONS: | 1. At elevated walking surfaces for access to, and use of, electrical, mechanical or plumbing systems or equipment, guards shall have balusters or be of solid materials such that a sphere with a diameter of 21 inches (533 mm) cannot pass through any opening. |
| 2. In occupancies in Group I-3, F, H or S, the clear distance between intermediate rails measured at right angles to the rails shall not exceed 21 inches (533 mm). | |
| 3. Approved existing open guards. |
| WITHOUT SPRINKLER SYSTEM | WITH SPRINKLER SYSTEMa | ||||
| OCCUPANCY | Stairways (inches per occupant) |
Other egress
components (inches per occupant) |
Stairways (inches per occupant) |
Other egress
components (inches per occupant) |
|
| Occupancies other than those listed below | 0.3 | 0.2 | 0.2 | 0.15 | |
| Hazardous: H-1, H-2, H-3 and H-4 | Not permitted | Not permitted | 0.3 | 0.2 | |
| Institutional: I-2 | Not permitted | Not permitted | 0.3 | 0.2 | |
| For SI: 1 inch = 25.4 mm. | |
| a. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. |
| EXCEPTIONS: | 1. The minimum and maximum width shall not apply to door openings that are not part of the required means of egress in occupancies in Groups R-2 and R-3. |
| 2. Door openings to storage closets less than 10 square feet (0.93 m2) in area shall not be limited by the minimum width. | |
| 3. Width of door leaves in revolving doors that comply with Section 1008.1.4.1 shall not be limited. | |
| 4. Door openings within a dwelling unit shall not be less than 78 inches (1981 mm) in height. | |
| 5. Exterior door openings in dwelling units, other than the required exit door, shall not be less than 76 inches (1930 mm) in height. | |
| 6. Exit access doors serving a room not larger than 70 square feet (6.5 m2) shall be not less than 24 inches (610 mm) in door width. |
| EXCEPTIONS: | 1. A revolving door is permitted to be used without an adjacent swinging door for street-floor elevator lobbies provided a stairway, escalator or door from other parts of the building does not discharge through the lobby and the lobby does not have any occupancy or use other than as a means of travel between elevators and a street. |
| 2. Existing revolving doors where the number of revolving doors does not exceed the number of swinging doors within 20 feet (6096 mm). |
| EXCEPTION: | Other stairs approved by the fire code official. |
| INSIDE DIAMETER | POWER-DRIVEN- TYPE SPEED CONTROL (RPM) |
MANUAL-TYPE
SPEED CONTROL (RPM) |
||
| 6' 6" | 11 | 12 | ||
| 7' 0" | 10 | 11 | ||
| 7' 6" | 9 | 11 | ||
| 8' 0" | 9 | 10 | ||
| 8' 6" | 8 | 9 | ||
| 9' 0" | 8 | 9 | ||
| 9' 6" | 7 | 8 | ||
| 10' 0" | 7 | 8 | ||
| For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. |
| EXCEPTION: | Aisle stairs provided with a center handrail are not required to have additional handrails. |
| EXCEPTION: | In buildings equipped throughout with an approved automatic sprinkler system, opening protection is not required. |
| EXCEPTION: | For fire escape stairs serving 10 or fewer occupants, an approved fire escape ladder is allowed to serve as the termination. |
| EXCEPTIONS: | 1. Corridors in occupancies other than in Group H, which are equipped throughout with an approved automatic sprinkler system. |
| 2. Patient room doors in corridors in occupancies in Group I-2 where smoke barriers are provided in accordance with the International Building Code. | |
| 3. Corridors in occupancies in Group E where each room utilized for instruction or assembly has at least one-half of the required means of egress doors opening directly to the exterior of the building at ground level. | |
| 4. Corridors that are in accordance with the International Building Code. |
| EXCEPTIONS: | 1. Where 20-minute fire door assemblies are required, solid wood doors at least 1.75 inches (44 mm) thick or insulated steel doors are allowed. |
| 2. Openings protected with fixed wire glass set in steel frames. | |
| 3. Openings covered with 0.5-inch (12.7 mm) gypsum wallboard or 0.75-inch (19.1 mm) plywood on the room side. | |
| 4. Opening protection is not required when the building is equipped throughout with an approved automatic sprinkler system. |
| EXCEPTION: | A dead-end passageway or corridor shall not be limited in length where the length of the dead-end passageway or corridor is less than 2.5 times the least width of the dead-end passageway or corridor. |
| EXCEPTION: | Stairs that continue one-half story beyond their levels of exit discharge need not be provided with barriers where the exit discharge is obvious. |
| EXCEPTIONS: | 1. Separation from the interior of the building is not required for buildings that are two stories or less above grade where the level of exit discharge serving such occupancies is the first story above grade. |
| 2. Separation from the interior of the building is not required where the exterior stairway is served by an exterior balcony that connects two remote exterior stairways or other approved exits, with a perimeter that is not less than 50 percent open. To be considered open, the opening shall be a minimum of 50 percent of the height of the enclosing wall, with the top of the opening not less than 7 feet (2134 mm) above the top of the balcony. | |
| 3. Separation from the interior of the building is not required for an exterior stairway located in a building or structure that is permitted to have unenclosed interior stairways in accordance with Section 1022. | |
| 4. Separation from the interior of the building is not required for exterior stairways connected to open-ended corridors, provided that: | |
| 4.1. The building, including corridors and stairs, is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. | |
| 4.2. The open-ended corridors comply with Section 1018. | |
| 4.3. The open-ended corridors are connected on each end to an exterior exit stairway complying with Section 1026. | |
| 4.4. At any location in an open-ended corridor where a change of direction exceeding 45 degrees occurs, a clear opening of not less than 35 square feet (3 m2) or an exterior stairway shall be provided. Where clear openings are provided, they shall be located so as to minimize the accumulation of smoke or toxic gases. |
| OCCUPANCY | COMMON PATH LIMIT | DEAD-END LIMIT | TRAVEL DISTANCE LIMIT | |||
| Unsprinklered (feet) |
Sprinklered (feet) |
Unsprinklered (feet) |
Sprinklered (feet) |
Unsprinklered (feet) |
Sprinklered (feet) |
|
| Group A | 20/75a | 20/75a | 20b | 20b | 200 | 250 |
| Group B | 75 | 100 | 50 | 50 | 200 | 250 |
| Group E | 75 | 75 | 20 | 50 | 200 | 250 |
| Group F-1, S-1d | 75 | 100 | 50 | 50 | 200 | 250 |
| Group F-2, S-2d | 75 | 100 | 50 | 50 | 300 | 400 |
| Group H-1 | 25 | 25 | 0 | 0 | 75 | 75 |
| Group H-2 | 50 | 100 | 0 | 0 | 75 | 100 |
| Group H-3 | 50 | 100 | 20 | 20 | 100 | 150 |
| Group H-4 | 75 | 75 | 20 | 20 | 150 | 175 |
| Group H-5 | 75 | 75 | 20 | 20 | 150 | 200 |
| Group I-1 | 75 | 75 | 20 | 50 | 200 | 250 |
| Group I-2 (Health Care) | NRe | NRe | NR | NR | 150 | 200c |
| Group I-3 (Detention and Correctional -- Use Conditions II, III, IV, V) | 100 | 100 | NR | NR | 150c | 200c |
| Group I-4 (Day Care Centers) | NR | NR | 20 | 20 | 200 | 250 |
| Group M (Covered Mall) | 75 | 100 | 50 | 50 | 200 | 400 |
| Group M (Mercantile) | 75 | 100 | 50 | 50 | 200 | 250 |
| Group R-1 (Hotels) | 75 | 75 | 50 | 50 | 200 | 250 |
| Group R-2 (Apartments) | 75 | 75 | 50 | 50 | 200 | 250 |
| Group R-3 (One- and Two-Family) | NR | NR | NR | NR | NR | NR |
| Group R-4 (Residential Care/Assisted Living) | NR | NR | NR | NR | NR | NR |
| Group U | 75 | 75 | 20 | 50 | 200 | 250 |
| For SI: 1 foot = 304.8 mm. | |
| a. 20 feet for common path serving 50 or more persons; 75 feet for common path serving less than 50 persons. | |
| b. See Section 1028.9.5 for dead-end aisles in Group A occupancies. | |
| c. This dimension is for the total travel distance, assuming incremental portions have fully utilized their allowable maximums. For travel distance within the room, and from the room exit access door to the exit, see the appropriate occupancy chapter. | |
| d. See the International Building Code for special requirements on spacing of doors in aircraft hangars. | |
| e. Any patient sleeping room, or any suite that includes patient sleeping rooms, of more than 1,000 square feet (93 m2) shall have at least two exit access doors placed a distance apart equal to not less than one-third of the length of the maximum overall diagonal dimension of the patient sleeping room or suite to be served, measured in a straight line between exit access doors. | |
| NR = No requirements. |
| EXCEPTION: | Thirty-six inches (914 mm) where the aisle serves less than 50 seats. |
| EXCEPTION: | Thirty inches (760 mm) for catchment areas serving not more than 60 seats. |
| EXCEPTION: | Thirty-six inches (914 mm) where the aisle serves less than 50 seats. |
| EXCEPTION: | Thirty inches (760 mm) for catchment areas serving not more than 60 seats. |
| EXCEPTION: | Open, unenclosed stairwells in historic buildings designated as historic under a state or local historic preservation program. |
| EXCEPTION: | Group U occupancies. |
| EXCEPTIONS: | 1. Vertical opening protection is not required for Group R-3 occupancies. |
| 2. Vertical opening protection is not required for open parking garages and ramps. | |
| 3. Vertical opening protection is not required for escalators. |
| EXCEPTIONS: | 1. Vertical opening protection is not required for Group R-3 occupancies. |
| 2. Vertical opening protection is not required for open parking garages and ramps. | |
| 3. Vertical opening protection is not required for escalators. |
![]() |
| EXCEPTIONS: | 1. Vertical opening protection is not required for Group R-3 occupancies. |
| 2. Vertical opening protection is not required for open parking garages and ramps. |
| EXCEPTION: | Occupancies with an existing, previously approved fire alarm system. |
| EXCEPTIONS: | 1. A manual fire alarm system is not required in a building with a maximum area of 1,000 square feet (93 m2) that contains a single classroom and is located no closer than 50 feet (15,240 mm) from another building. |
| 2. A manual fire alarm system is not required in Group E occupancies with an occupant load less than 50. |
| EXCEPTIONS: | 1. Manual fire alarm boxes in resident or patient sleeping areas shall not be required at exits if located at all nurses' control stations or other constantly attended staff locations, provided such stations are visible and continuously accessible and that travel distances required in Section 907.5.2 are not exceeded. |
| 2. Where each sleeping room has a means of egress door opening directly to an exterior egress balcony that leads directly to the exits in accordance with WAC 51-50-1019, and the building is not more than three stories in height. |
| EXCEPTION: | Manual fire alarm boxes in resident or patient sleeping areas shall not be required at exits if located at all nurses' control stations or other constantly attended staff locations, provided such stations are visible and continuously accessible and that travel distances required in Section 907.5.2.1 are not exceeded. |
| EXCEPTIONS: | 1. Buildings less than two stories in height where all sleeping units, attics and crawl spaces are separated by 1-hour fire-resistance-rated construction and each sleeping unit has direct access to a public way, exit court or yard. |
| 2. Manual fire alarm boxes are not required throughout the building when the following conditions are met: | |
| 2.1. The building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2; | |
| 2.2. The notification appliances will activate upon sprinkler water flow; and | |
| 2.3. At least one manual fire alarm box is installed at an approved location. |
| EXCEPTION: | An automatic smoke detection system is not required in buildings that do not have interior corridors serving sleeping units and where each sleeping unit has a means of egress door opening directly to an exit or to an exterior exit access that leads directly to an exit. |
| EXCEPTION: | Buildings less than two stories in height where all sleeping units, attics and crawl spaces are separated by 1-hour fire-resistance-rated construction and each sleeping unit has direct access to a public way, exit court or yard. |
| EXCEPTION: | Buildings equipped with single-station smoke alarms meeting or exceeding the requirements of Section 907.2.10.1 and where the fire alarm system includes at least one manual fire alarm box per floor arranged to initiate the alarm. |
| EXCEPTIONS: | 1. Where each living unit is separated from other contiguous living units by fire barriers having a fire-resistance rating of not less than 0.75 hour, and where each living unit has either its own independent exit or its own independent stairway or ramp discharging at grade. |
| 2. A separate fire alarm system is not required in buildings that are equipped throughout with an approved supervised automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 and having a local alarm to notify all occupants. | |
| 3. A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units and are protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, provided that dwelling units either have a means of egress door opening directly to an exterior exit access that leads directly to the exits or are served by open-ended corridors designed in accordance with Section 1023.6, Exception 4. |
| EXCEPTIONS: | 1. Where there are interconnected smoke alarms meeting the requirements of Section 907.2.11 and there is at least one manual fire alarm box per floor arranged to continuously sound the smoke alarms. |
| 2. Other manually activated, continuously sounding alarms approved by the fire code official. |
| EXCEPTIONS: | 1. Interconnection is not required in buildings that are not undergoing alterations, repairs or construction of any kind. |
| 2. Smoke alarms in existing areas are not required to be interconnected where alterations or repairs do not result in the removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available which could provide access for interconnection without the removal of interior finishes. |
| EXCEPTIONS: | 1. Smoke alarms are permitted to be solely battery operated in existing buildings where no construction is taking place. |
| 2. Smoke alarms are permitted to be solely battery operated in buildings that are not served from a commercial power source. | |
| 3. Smoke alarms are permitted to be solely battery operated in existing areas of buildings undergoing alterations or repairs that do not result in the removal of interior walls or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available which could provide access for building wiring without the removal of interior finishes. |
| EXCEPTIONS: | 1. Work involving the exterior surfaces of dwellings, such as the replacement of roofing or siding, or the addition or replacement of windows or doors, or the addition of a porch or deck, or electrical permits. |
| 2. Installation, alteration or repairs of noncombustion plumbing or mechanical systems. | |
| 3. Sleeping units or dwelling units in R-1 occupancies and R-2 college dormitories, hotel, and DSHS licensed boarding home and residential treatment facility occupancies which do not themselves contain a fuel-burning appliance, a fuel-burning fireplace, or have an attached garage, but which are located in a building with a fuel-burning appliance, a fuel-burning fireplace, or an attached garage, need not be provided with carbon monoxide alarms provided that: | |
| a. The sleeping units or dwelling unit is not adjacent to any room which contains a fuel-burning appliance, a fuel-burning fireplace, or an attached garage; and | |
| b. The sleeping units or dwelling unit is not connected by duct work or ventilation shafts with a supply or return register in the same room to any room containing a fuel-burning appliance, a fuel-burning fireplace, or to an attached garage; and | |
| c. The building is provided with a common area carbon monoxide detection system. | |
| d. An open parking garage, as defined in the International Building Code, or enclosed parking garage ventilated in accordance with Section 404 of the International Mechanical Code shall not be deemed to be an attached garage. |
| EXCEPTION: | Means of egress conforming to the requirements of the building code under which they were constructed and Section 1030 shall not be required to comply with 4604.2 through 4604.21. |
| EXCEPTIONS: | 1. Elevators used as an accessible means of egress where allowed by Section 1007.4. |
| 2. Previously approved escalators and moving walks in existing buildings. |
| EXCEPTION: | Approved self-luminous signs that provide evenly illuminated letters shall have a minimum luminance of 0.06 foot-lamberts (0.21 cd/m2). |
| EXCEPTION: | Approved signs that provide continuous illumination independent of external power sources are not required to be connected to an emergency electrical system. |
| EXCEPTION: | Assembly occupancies used exclusively as a place of worship and having an occupant load of less than 300. |
| EXCEPTION: | Buildings used only during daylight hours which are provided with windows for natural light in accordance with the International Building Code. |
| EXCEPTION: | Buildings less than 3,000 square feet (279 m2) in gross sales area on one story only, excluding mezzanines. |
| EXCEPTION: | Where each sleeping unit has direct access to the outside of the building at grade. |
| EXCEPTION: | Where each dwelling unit or sleeping unit has direct access to the outside of the building at grade. |
| EXCEPTION: | Where each sleeping unit has direct access to the outside of the building at ground level. |
| EXCEPTIONS: | 1. Existing guards on the open side of stairs shall be not less than 30 inches (760 mm) high. |
| 2. Existing guards within dwelling units shall be not less than 36 inches (910 mm) high. | |
| 3. Existing guards in assembly seating areas. |
| EXCEPTIONS: | 1. At elevated walking surfaces for access to, and use of, electrical, mechanical or plumbing systems or equipment, guards shall have balusters or be of solid materials such that a sphere with a diameter of 21 inches (533 mm) cannot pass through any opening. |
| 2. In occupancies in Group I-3, F, H or S, the clear distance between intermediate rails measured at right angles to the rails shall not exceed 21 inches (533 mm). | |
| 3. Approved existing open guards. |
| WITHOUT SPRINKLER SYSTEM | WITH SPRINKLER SYSTEMa | ||||
| OCCUPANCY | Stairways (inches per occupant) |
Other egress
components (inches per occupant) |
Stairways (inches per occupant) |
Other egress
components (inches per occupant) |
|
| Occupancies other than those listed below | 0.3 | 0.2 | 0.2 | 0.15 | |
| Hazardous: H-1, H-2, H-3 and H-4 | Not permitted | Not permitted | 0.3 | 0.2 | |
| Institutional: I-2 | Not permitted | Not permitted | 0.3 | 0.2 | |
| For SI: 1 inch = 25.4 mm. | |
| a. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. |
| EXCEPTIONS: | 1. The minimum and maximum width shall not apply to door openings that are not part of the required means of egress in occupancies in Groups R-2 and R-3. |
| 2. Door openings to storage closets less than 10 square feet (0.93 m2) in area shall not be limited by the minimum width. | |
| 3. Width of door leaves in revolving doors that comply with Section 1008.1.4.1 shall not be limited. | |
| 4. Door openings within a dwelling unit shall not be less than 78 inches (1981 mm) in height. | |
| 5. Exterior door openings in dwelling units, other than the required exit door, shall not be less than 76 inches (1930 mm) in height. | |
| 6. Exit access doors serving a room not larger than 70 square feet (6.5 m2) shall be not less than 24 inches (610 mm) in door width. |
| EXCEPTIONS: | 1. A revolving door is permitted to be used without an adjacent swinging door for street-floor elevator lobbies provided a stairway, escalator or door from other parts of the building does not discharge through the lobby and the lobby does not have any occupancy or use other than as a means of travel between elevators and a street. |
| 2. Existing revolving doors where the number of revolving doors does not exceed the number of swinging doors within 20 feet (6096 mm). |
| EXCEPTION: | Other stairs approved by the fire code official. |
| INSIDE DIAMETER | POWER-DRIVEN- TYPE SPEED CONTROL (RPM) |
MANUAL-TYPE
SPEED CONTROL (RPM) |
||
| 6' 6" | 11 | 12 | ||
| 7' 0" | 10 | 11 | ||
| 7' 6" | 9 | 11 | ||
| 8' 0" | 9 | 10 | ||
| 8' 6" | 8 | 9 | ||
| 9' 0" | 8 | 9 | ||
| 9' 6" | 7 | 8 | ||
| 10' 0" | 7 | 8 | ||
| For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. |
| EXCEPTION: | Aisle stairs provided with a center handrail are not required to have additional handrails. |
| EXCEPTION: | In buildings equipped throughout with an approved automatic sprinkler system, opening protection is not required. |
| EXCEPTION: | For fire escape stairs serving 10 or fewer occupants, an approved fire escape ladder is allowed to serve as the termination. |
| EXCEPTIONS: | 1. Corridors in occupancies other than in Group H, which are equipped throughout with an approved automatic sprinkler system. |
| 2. Patient room doors in corridors in occupancies in Group I-2 where smoke barriers are provided in accordance with the International Building Code. | |
| 3. Corridors in occupancies in Group E where each room utilized for instruction or assembly has at least one-half of the required means of egress doors opening directly to the exterior of the building at ground level. | |
| 4. Corridors that are in accordance with the International Building Code. |
| EXCEPTIONS: | 1. Where 20-minute fire door assemblies are required, solid wood doors at least 1.75 inches (44 mm) thick or insulated steel doors are allowed. |
| 2. Openings protected with fixed wire glass set in steel frames. | |
| 3. Openings covered with 0.5-inch (12.7 mm) gypsum wallboard or 0.75-inch (19.1 mm) plywood on the room side. | |
| 4. Opening protection is not required when the building is equipped throughout with an approved automatic sprinkler system. |
| EXCEPTION: | A dead-end passageway or corridor shall not be limited in length where the length of the dead-end passageway or corridor is less than 2.5 times the least width of the dead-end passageway or corridor. |
| EXCEPTION: | Stairs that continue one-half story beyond their levels of exit discharge need not be provided with barriers where the exit discharge is obvious. |
| EXCEPTIONS: | 1. Separation from the interior of the building is not required for buildings that are two stories or less above grade where the level of exit discharge serving such occupancies is the first story above grade. |
| 2. Separation from the interior of the building is not required where the exterior stairway is served by an exterior balcony that connects two remote exterior stairways or other approved exits, with a perimeter that is not less than 50 percent open. To be considered open, the opening shall be a minimum of 50 percent of the height of the enclosing wall, with the top of the opening not less than 7 feet (2134 mm) above the top of the balcony. | |
| 3. Separation from the interior of the building is not required for an exterior stairway located in a building or structure that is permitted to have unenclosed interior stairways in accordance with Section 1022. | |
| 4. Separation from the interior of the building is not required for exterior stairways connected to open-ended corridors, provided that: | |
| 4.1. The building, including corridors and stairs, is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. | |
| 4.2. The open-ended corridors comply with Section 1018. | |
| 4.3. The open-ended corridors are connected on each end to an exterior exit stairway complying with Section 1026. | |
| 4.4. At any location in an open-ended corridor where a change of direction exceeding 45 degrees occurs, a clear opening of not less than 35 square feet (3 m2) or an exterior stairway shall be provided. Where clear openings are provided, they shall be located so as to minimize the accumulation of smoke or toxic gases. |
| OCCUPANCY | COMMON PATH LIMIT | DEAD-END LIMIT | TRAVEL DISTANCE LIMIT | |||
| Unsprinklered (feet) |
Sprinklered (feet) |
Unsprinklered (feet) |
Sprinklered (feet) |
Unsprinklered (feet) |
Sprinklered (feet) |
|
| Group A | 20/75a | 20/75a | 20b | 20b | 200 | 250 |
| Group B | 75 | 100 | 50 | 50 | 200 | 250 |
| Group E | 75 | 75 | 20 | 50 | 200 | 250 |
| Group F-1, S-1d | 75 | 100 | 50 | 50 | 200 | 250 |
| Group F-2, S-2d | 75 | 100 | 50 | 50 | 300 | 400 |
| Group H-1 | 25 | 25 | 0 | 0 | 75 | 75 |
| Group H-2 | 50 | 100 | 0 | 0 | 75 | 100 |
| Group H-3 | 50 | 100 | 20 | 20 | 100 | 150 |
| Group H-4 | 75 | 75 | 20 | 20 | 150 | 175 |
| Group H-5 | 75 | 75 | 20 | 20 | 150 | 200 |
| Group I-1 | 75 | 75 | 20 | 50 | 200 | 250 |
| Group I-2 (Health Care) | NRe | NRe | NR | NR | 150 | 200c |
| Group I-3 (Detention and Correctional -- Use Conditions II, III, IV, V) | 100 | 100 | NR | NR | 150c | 200c |
| Group I-4 (Day Care Centers) | NR | NR | 20 | 20 | 200 | 250 |
| Group M (Covered Mall) | 75 | 100 | 50 | 50 | 200 | 400 |
| Group M (Mercantile) | 75 | 100 | 50 | 50 | 200 | 250 |
| Group R-1 (Hotels) | 75 | 75 | 50 | 50 | 200 | 250 |
| Group R-2 (Apartments) | 75 | 75 | 50 | 50 | 200 | 250 |
| Group R-3 (One- and Two-Family) | NR | NR | NR | NR | NR | NR |
| Group R-4 (Residential Care/Assisted Living) | NR | NR | NR | NR | NR | NR |
| Group U | 75 | 75 | 20 | 50 | 200 | 250 |
| For SI: 1 foot = 304.8 mm. | |
| a. 20 feet for common path serving 50 or more persons; 75 feet for common path serving less than 50 persons. | |
| b. See Section 1028.9.5 for dead-end aisles in Group A occupancies. | |
| c. This dimension is for the total travel distance, assuming incremental portions have fully utilized their allowable maximums. For travel distance within the room, and from the room exit access door to the exit, see the appropriate occupancy chapter. | |
| d. See the International Building Code for special requirements on spacing of doors in aircraft hangars. | |
| e. Any patient sleeping room, or any suite that includes patient sleeping rooms, of more than 1,000 square feet (93 m2) shall have at least two exit access doors placed a distance apart equal to not less than one-third of the length of the maximum overall diagonal dimension of the patient sleeping room or suite to be served, measured in a straight line between exit access doors. | |
| NR = No requirements. |
| EXCEPTION: | Thirty-six inches (914 mm) where the aisle serves less than 50 seats. |
| EXCEPTION: | Thirty inches (760 mm) for catchment areas serving not more than 60 seats. |
| EXCEPTION: | Thirty-six inches (914 mm) where the aisle serves less than 50 seats. |
| EXCEPTION: | Thirty inches (760 mm) for catchment areas serving not more than 60 seats. |
| EXCEPTION: | Open, unenclosed stairwells in historic buildings designated as historic under a state or local historic preservation program. |